4. Device reset: When the device reports a fire alarm and the control panel responds, it can be reset by
operating the control panel . After the detector receives the reset signal, it will perform the reset operation.
5. Restore factory settings: After the detector is connected to the network, when it is powered on again, the red
indicators will be on for 10s; during this period, the factory settings can be restored by pressing the button five
times.
Note: The button function only has one click, three consecutive clicks, five consecutive clicks, long press function,
and other button methods are invalid.
VIII. General failure and repair
General faults and their solutions are shown in the table below
Reason
Solution
The device is not connected to the
network
Restart the network operation
Too far away from the control panel
or interference sources nearby
Move the device near the controller,
reconnect to the network and remove
the source of interference
Low battery or no battery inserted
Replace battery
IX. Maintenance
1. The detector should take corresponding moisture-proof and anti-corrosion measures.
2. The detector is cleaned at least once a year to ensure the normal operation of the system. Before the
detector is cleaned, the relevant management department should be notified that the system will be
maintained, and the logical control function of the area or the system that will be maintained should be closed
to avoid unnecessary alarm linkage.
3. The detector should conduct a simulated fire alarm test every six months to test whether the detector works
normally.
10. Matters needing attention
1. The horizontal distance between the detector and the air supply hole of the air conditioner should not be
less than 1.5m.
2. The horizontal distance from the detector to the wall and beam side should not be less than 0.5m.
3. The detector should be installed horizontally. If it must be installed at an angle, the inclination angle should
not be greater than 45°.
4. When the detectors are installed on the ceiling of the inner walkway with a width less than 3m, they should
be arranged in the center, and the installation distance of the temperature sensing detectors should not exceed
10m.
5. After the signal passes through the wall, the signal strength will be greatly attenuated, so try to reduce the
number of partition walls for wireless products.
6. When installing the product, keep it away from metal to reduce the shielding of the signal from metal objects.
For example, it cannot be installed in a metal box such as a fire hydrant box or outside of a metal cabinet.
7. Install in a low-interference environment and far away from motors or large-scale electrical equipment.