Please read this user manual carefully before installation. TCMK5411W Wireless Input Module User Manual Liaoning·Tiancheng Fire Protection Equipment Co.
Version Date Author Note Ver1.
I. General TCMK5411W wireless input module (hereinafter referred to as the module) is suitable for installation in public places, factories and other environments. When there is a fire alarm, after the module receives the input signal specified by the manufacturer, it will send an alarm signal to the control panel through wireless communication technology, and the red light will always be on.
II. Features 1. Adopting 470MHz wireless communication technology, no need to pre-buried wiring, easy and quick engineering installation; 2. With battery low-voltage detection function, it can reflect the battery power status in time; 3. Use microprocessor to realize signal processing, and use digital signal to communicate with controller, work stably and reliably, and have good suppression ability against electromagnetic interference. III. Technical specifications 1. Battery type: CR17450(wired) 2.
6. Communication method: 470MHz FSK coded two-way communication 7. Communication distance:≤50m 8. Transmitted power:<20dBm 9. Reset method: by control panel 10.Application environment: Type:indoor Atmosphere pressure:86kPa~106kPa Temperature:-10℃~+55℃ Relative humidity≤95%,non-condensing 11.Outline dimension:101mm×137mm×43mm 12.Material and color:ABS, off-white 13. Weight: about 160g (including battery) 14.
When there is a fire alarm, after the module receives the closing signal, it will send relevant information signals to the controller through wireless communication technology. After the controller responds to the information signal, the red light of the input module is always on. When the battery of the input module is low, the module sends a battery undervoltage signal to the controller, and the Fault Indicator flashes twice every 48 seconds. V. Installation method 1.
Fig. 3 Installation hole distance AS1, AS2: Passive answer signal input Fig. 4 Wiring diagram Test Warning: Please make sure that the polarity of the battery is correct before proceeding. 1. The input module should be tested every year after installation and during use. 2. Input signal test: After the networking is successful, the relevant input signal conditions of the input module are artificially satisfied (please turn off the fire alarm linkage function to avoid unnecessary alarm linkage).
VI. Use and operation 1. Network segment setting: The device network segment should be set before the input module enters the network. In the network setting interface of the controller menu, set the input module network segment according to the actual situation on site. 2.
times. Button, the yellow light flashes once for the feedback mode, the yellow light flashes twice for the supervision mode, and the yellow light flashes for three times for the fire alarm mode. VII.
Liaoning·Yingkou Tiancheng Fire Equipment Co., Ltd. Address: No. 11-2, Kechechang Xili, Xishi District, Yingkou, Pilot Free Trade Zone (Liaoning) China , City Fax: 0417-4835568 Postcode: 115004 Tel:400-6930-119 Email: info@tcfiretech.com Website: www.tcfiretech.