TS4-F Installation Manual TS4-F, TS4-A-F, TS4-A-2F and RSS Transmitter
IMPORTANT SAFETY INSTRUCTIONS LETHAL VOLTAGE MAY BE PRESENT IN ANY PV INSTALLATION SAVE THESE INSTRUCTIONS WARNING - THIS PHOTOVOLTAIC RAPID SHUTDOWN EQUIPMENT (PVRSE) DOES NOT PERFORM ALL OF THE FUNCTIONS OF A COMPLETE PHOTOVOLTAIC RAPID SHUTDOWN SYSTEM (PVRSS). THIS PVRSE MUST BE INSTALLED WITH OTHER EQUIPMENT TO FORM A COMPLETE PVRSS THAT MEETS THE REQUIREMENTS OF NEC (NFPA 70) SECTION 690.12 FOR CONTROLLED CONDUCTORS OUTSIDE THE ARRAY.
TABLE OF CONTENTS TS4-F Rapid Shutdown System 4 Technical Specifications – TS4-A-2F 25 System Overview: TS4-F 5 Technical Specifications – RSS Transmitter 26 System Overview: TS4-A-F 6 System Overview: TS4-A-2F 7 Technical Specifications – RSS Transmitter Commercial Kit 27 Installation Notes 8 Technical Specifications – RSS Transmitter Outdoor Kit 28 TS4-F Installation 9 Testing Rapid Shutdown 29 Troubleshooting 30 TS4-A-F Installation 10 TS4-A-2F Installation 11 Conduit Drilling G
TS4-F RAPID SHUTDOWN SYSTEM Tigo’s TS4-F (or TS4-A-F, TS4-A-2F) and RSS Transmitter are a UL-certified PVRSS (Photovoltaic Rapid Shutdown System) when installed together. The RSS Transmitter supplies a keep-alive signal along one of the DC homeruns of the string and the TS4-F units on each module will shut down when the Transmitter is switched off. The TS4-F, TS4-A-F and TS4-A-2F can be used interchangeably in the same system. Module-Level Power Electronics: TS4-F • NEC 2017 and 2020 690.
SYSTEM OVERVIEW: TS4-F TS4-F TS4-F • Module electronics are contained in the junction box, installed at the PV module factory. • Connected in series like regular modules • No additional wiring connections to make 1 2 3 Rapid Shutdown System Transmitter 1. Modules with integrated TS4-F 2. RSS Transmitter and RSS Core 3. UL PVRSS Listed Inverter The TS4-F requires a Tigo RSS Transmitter or inverter with built-in transmitter for operation.
SYSTEM OVERVIEW: TS4-A-F TS4-A-F • Bracket clips to module frame without tools • TS4-A outputs are connected in series to form a string • No additional grounding required 1 2 3 Tigo Rapid Shutdown TS4-A-F 4 - 123A DO NOT DISCONNECT UNDER LOAD Rapid Shutdown System Transmitter 1. Modules with TS4-A-F add-on 2. RSS Transmitter and RSS Core 3.
SYSTEM OVERVIEW: TS4-A-2F TS4-A-2F • Bracket clips to module frame without tools • TS4-A outputs are connected in series to form a string • No additional grounding required • Two individual module inputs 1 2 3 Tigo Rapid Shutdown TS4-A-2F 4 - 123A DO NOT DISCONNECT UNDER LOAD Rapid Shutdown System Transmitter 1. Modules with TS4-A-2F add-on 2. RSS Transmitter and RSS Core 3.
INSTALLATION NOTES • TS4-F, TS4-A-F, and TS4-A-2F are shipped in the OFF position and will measure 0.6V at the output when the keep-alive signal is not present. • Failing to follow the sequence of installation steps may result in TS4 damage not covered under warranty. • Connect all TS4-A-F or TS4-A-2F units to their respective modules before connecting their outputs in series. • Install all TS4-F, TS4-A-F, or TS4-A-2F units before powering on the RSS Transmitter.
TS4-F INSTALLATION Smart modules with an integrated TS4 Junction box are installed and connected in series just like standard PV modules. Connect modules with TS4-F in series before powering on the RSS Transmitter. 1 TS4-F 4 - 123A TS4-F 4 - 123A 2 TS4-F 4 - 123A TS4-F 4 - 123A RSS Transmitter must be powered OFF during TS4-F installation.
TS4-A-F INSTALLATION Standard modules can be equipped with TS4-A-F add-on units as shown below. Always connect modules to TS4-A inputs before connecting outputs. Each TS4-A-F must have a PV module connected to its input before connecting the outputs of TS4-A-F units in series. To disconnect TS4-A-F from a module, disconnect the TS4-A-F outputs from the string before disconnecting the TS4-A-F inputs from the module junction box.
TS4-A-2F INSTALLATION Standard modules can be equipped with TS4-A-2F add-on units as shown below. Always connect modules to TS4-A inputs before connecting outputs. Each TS4-A-2F must have a PV module connected to its inputs before connecting the outputs of TS4-A-2F units in series. To disconnect TS4-A-2F from a module, disconnect the TS4-A-2F outputs from the string before disconnecting the TS4-A-2F inputs from the module junction box.
PV CONDUCTOR INSTALLATION - MULTI-TRANSMITTER SYSTEMS REQUIRED PRACTICES When installing a system with 2 or more transmitters it is mandatory to use the following best installation practices of PLC circuits to ensure a troublefree installation. Run +/- string conductors from the same transmitter together in the same conduit. >8” (20cm) Run +/- string conductors from the same string together through array and conduit. The closer the conduit or cable tray the greater potential for crosstalk to occur.
MAINTAIN SIGNAL INTEGRITY The following practices will help maintain signal integrity for all PLC rapid shutdown systems. In order to maintain signal integrity, the RSS Transmitter has a specified maximum round-trip distance from positive to negative of 300m (985ft). If the longest string in a system exceeds 300m, but is less than 500m, two cores may be used in series on the string to amplify the signal. Contact Tigo Sales Engineers for more information and assistance in these applications.
RSS TRANSMITTER INSTALLATION – SINGLE RSS CORE 85-264V AC LED (Power) PSU +VIN GND Rapid No Connection Shutdown LOCK OUT TAG OUT 1 + 2 System Transmitter - N L Rapid Shutdown System Transmitter LED (Signal) RSS Core inputs 3 1 DIN Rail PSU 2 RSS Transmitter 3 RSS Core (CT) Transmitter power supply must be on same AC branch circuit as inverter to meet rapid shutdown requirements.
RSS TRANSMITTER WIRING – SINGLE RSS CORE LOCK OUT TAG OUT + L - N Rapid Shutdown System Transmitter AC Wires for Power Supply Homerun Only (+) or (-) through RSS Core Note: Install TS4-F before powering on RSS Transmitter · Pass either positive or negative homerun through RSS Core · Connect wires to AC side of power supply Max number of strings per RSS Core: 10 Max string length: 30 modules Max current per RSS Core: 100A Max cable length from inverter (+) to inverter (-): 1000ft (300m) For longer d
RSS TRANSMITTER GROUNDING – SINGLE RSS CORE DC Ground LOCK OUT TAG OUT AC Ground + L - N Rapid Shutdown System Transmitter Conduit Ground Note: Install TS4-F before powering on RSS Transmitter · Connect AC and DC ground wires to DIN rail · Ground all conduit connections · Turn on AC power to Transmitter power supply to activate keep-alive signal and energize PV array Warning: nonmetallic enclosure does not provide bonding between conduit connections. Use grounding type bushings and jumper wires.
RSS TRANSMITTER INSTALLATION – DUAL RSS CORE LED (Power) +VIN GND Rapid No Connection Shutdown LOCK OUT TAG OUT 1 + 2 System Transmitter - N L Rapid Shutdown System Transmitter 4 RSS Core inputs LED (Signal) RSS Core inputs 3 1 DIN Rail PSU 2 RSS Transmitter 3 RSS Core (CT) 4 RSS Core (CT) RSS Core polarity marking Match RSS Core polarity to ensure PLC signal flow in the correct direction.
RSS TRANSMITTER WIRING – DUAL RSS CORE LOCK OUT TAG OUT Rapid Shutdown System Transmitter + L - N Rapid Shutdown System Transmitter AC Wires for Power Supply Homerun Only (+) or (-) through RSS Core Homerun Keep same polarity for all homeruns and RSS Cores throughout the installation Note: Install TS4-F before powering on RSS Transmitter · Pass either positive or negative homerun through RSS Cores · Connect wires to AC side of power supply Max number of strings per RSS Core: 10 Max string length:
RSS TRANSMITTER GROUNDING – DUAL RSS CORE DC Ground LOCK OUT TAG OUT AC Ground Rapid Shutdown System Transmitter + L - N Rapid Shutdown System Transmitter Conduit Ground Note: Install TS4-F before powering on RSS Transmitter · Connect AC and DC ground wires to DIN rail · Ground all conduit connections · Turn on AC power to Transmitter power supply to activate keep-alive signal Warning: nonmetallic enclosure does not provide bonding between conduit connections.
RSS TRANSMITTER COMMERCIAL INSTALLATION 200-500VAC Power Supply LED (Power) +VIN +12VDC GND -12VDC Rapid No Connection Shutdown -V +V + V ADJ + 1 2 - N L Rapid Shutdown System Transmitter RSS Core inputs LED (Signal) RSS Core inputs G L2 L1 Ground Neutral 1 DIN Rail PSU System Transmitter 4 3 2 RSS Transmitter 3 RSS Core (CT) 4 RSS Core (CT) Transmitter power supply must be on same AC branch circuit as inverter to meet rapid shutdown requirements.
RSS TRANSMITTER COMMERCIAL WIRING Match RSSRapid Core polarity to ensureShutdown PLC signal flow Systemdirection.
Appendix TS4-F, TS4-A-F, TS4-A-2F, RSS Transmitter
TECHNICAL SPECIFICATIONS – TS4-F Electrical Ratings TS4-F Fire Safety Input Rated DC Input Power 475W Input Voltage 16 - 90V Max Continuous Input Current (IMAX) 12.5A Output Output Power Range 0 - 475W Output Voltage Range 0 – VOC Communication Type Power Line Communication (PLC) Rapid Shutdown UL Listed (NEC 2017 & 2020 690.
TECHNICAL SPECIFICATIONS – TS4-A-F (500W) Specifications TS4-A-F Fire Safety Environmental Operating Temperature Range -30°C to +70°C (-22°F to +158°F) Outdoor Rating IP68, NEMA 3R Mechanical Dimensions W= 138.4mm, L= 139.7mm, H= 22.9mm Weight 490g Electrical Input Voltage 16 - 80V Maximum Continuous Input Current (IMAX) 15A Maximum Power 500W Output Cable Length 1.
TECHNICAL SPECIFICATIONS – TS4-A-F (700W) Specifications TS4-A-F Fire Safety Environmental UL: -30°C to +70°C (-22°F to +158°F) Operating Temperature Range IEC: -30°C to +70°C (-22°F to +158°F) Outdoor Rating IP68, NEMA 3R Mechanical Dimensions W= 138.4mm, L= 139.7mm, H= 22.9mm Weight 490g Electrical Input Voltage 16 - 80V Maximum Continuous Input Current (IMAX) 15A Maximum Power 700W Output Cable Length 1.
TECHNICAL SPECIFICATIONS – TS4-A-2F Specifications TS4-A-2F Fire Safety Environmental Operating Temperature Range -30°C to +70°C (-22°F to +158°F) Outdoor Rating IP68, NEMA 3R Mechanical Dimensions 138.4mm x 139.7mm x 22.9mm Weight 590g Electrical Voltage Range (per input)1 16 - 80V Maximum Current (per input) 15A Maximum Power (total) 1000W Output Cable Length 1.2m (portrait) or 2.
TECHNICAL SPECIFICATIONS – RSS TRANSMITTER Electrical Ratings RSS Transmitter Input Input Voltage 12VDC (+/- 2%) Input Current 1A Average Supply Power 0.85W Dimensions(Transmitter only) 90.2mm x 36.3mm x 57.
TECHNICAL SPECIFICATIONS – RSS TRANSMITTER COMMERCIAL KIT Electrical Ratings RSS Transmitter Input Input Voltage 12VDC (+/- 2%) Input Current 1A Average Supply Power 0.85W Included Power Supply Rating 480/277VAC input, 12VDC output Dimensions(Transmitter only) 90.2mm x 36.3mm x 57.
TECHNICAL SPECIFICATIONS – RSS TRANSMITTER OUTDOOR KIT Electrical Ratings RSS Transmitter Input Input Voltage 12VDC (+/- 2%) Input Current 1A Average Supply Power 0.85W Dimensions(Transmitter only) 90.2mm x 36.3mm x 57.
TESTING RAPID SHUTDOWN TS4-F (or TS4-A-F, TS4-A-2F) and an RSS Transmitter are a solution to meet NEC 2017 & 2020 690.12 Rapid Shutdown requirements. TS4-F, TS4-A-F, and TS4-A-2F units automatically enter rapid shutdown mode when the RSS Transmitter is switched off and resume energy production when power is restored to the RSS Transmitter. Wait 30 seconds after rapid shutdown activation before disconnecting DC cables or turning off DC disconnect.
TROUBLESHOOTING TS4-F/TS4-A-F/TS4-A-2F: • • • Output voltage without active transmitter signal is 0.
CONDUIT DRILLING GUIDE Enclosure Drilling Guide for .75" Conduit Single Core Dual Core 41.6 41.6 68 41.6 108 41.6 47.1 47.1 2X Ø 28 40 40 47.1 47.1 Ø 28 3X Ø 28 2X Ø 28 Enclosure Drilling Guide for 1" Conduit Single Core Dual Core 41.6 41.6 41.6 52.3 104.5 50.6 2X Ø 35 41.6 50.6 52.3 52.3 50.6 50.
MISCELLANEOUS Este equipamento não tem direito à proteção contra interferência prejudicial e não pode causar interferência em sistemas devidamente autorizados.
INSTALLATION COMPLETE Problems? TS4-F Troubleshooting Guide For more details on designing and installing solutions powered by Tigo, please visit: Tigo Academy Resource Center Or contact us at: training@tigoenergy.com Tigo Energy, Inc. 655 Campbell Technology Pkwy Suite 150, Campbell, California 95008 USA www.tigoenergy.com P: +1.408.402.0802 F:+1.408.358.6279 | sales@tigoenergy.