3.4 Setting parameters
If using connection 1 the following parameters must be set.
Table 10 - Parameters 10 to 85
No.
Parameter name
Value range
Default
Description
10, 20, …
Port mode
Deactivated
Deactivated
The port is inactive. L+ is turned off,
Input and Output Process Data is 0.
Cyclic
Target mode based on user defined configuration
including validation of Vendor ID, Device ID, and
Revision.
Roaming
Target mode without configuration, Validation:
No Device Check
11, 21, …
Validation and
backup
No Device check
No Device
check
There is no device check for validation or backup of
connected IO-Link Slave devices (default).
Type compare*,
no Backup/
Restore
A device check is performed for validation of
connected IO-Link Slave devices to the specified
device type, without backup/restore.
Type compare*,
Backup only"
A device check is performed for validation or backup
of connected IO-Link Slave devices to the specified
device type, without restore.
Type compare*,
Restore only
A device check is performed for validation or restore
of connected IO-Link Slave devices to the specified
device type, without backup.
Type compare*,
Backup and
Restore
A device check is performed for validation or
backup/restore of connected IO-Link Slave devices to
the specified device type.
No type
compare*, no
Backup/Restore
A device check is performed for validation of
connected IO-Link Slave devices,
without type compare, without backup/restore.
No type
compare*,
Backup only
A device check is performed for validation or
backup of connected IO-Link Slave devices,
without type compare, without restore.
No type
compare*,
Restore only
A device check is performed for validation or
restore of connected IO-Link Slave devices,
without type compare, without backup.
No type
compare*,
Backup and
Restore
A device check is performed for validation or
backup/restore of connected IO-Link Slave
devices,
without type compare.
13, 23, …
Port cycle time
0 ... 255
0
See table Calculation of the port cycle
time [} page 42].
14, 24, …
Vendor ID
0 … 65535
0
Vendor ID
See the documentation of the manufacturer of the
sensor/actuator used.
15, 25, …
Device ID
0 4294967295
0
Device ID
See the documentation of the manufacturer of the
sensor/actuator used.
Table 11 - Parameter 90
No.
Parameter name
Value range
Default
Description
90
DIO process data
layout
Port based (IQ/
CQ, IQ/CQ, IQ/
CQ, …)
Port based
Sequence of the process data of the digital inputs and
the digital outputs: Port 1 (Bit 0 and 1), Port 2
(Bit 2 and 3), ..., Port 8 (Bit 14 and 15). For each port
first pin 4 then pin 2 is transmitted.
Pin Based (IQ,
IQ, IQ, …
CQ, CQ, CQ, …)
The sequence of the process data of the digital inputs
and the digital outputs: Pin 4 (Port 1 to 8), pin 2 (Port
1 to 8).