User's Manual

TigoMaster 2TH User Manual
Page 28 of 36
CONFIDENTIAL
Copyright © 2020 CoreTigo Ltd.
4.
Communication
4.1 Process data
This section describes the process data for
- Connection 1 (Exclusive Owner - 32 bytes per IO-Link Port with Config)
- Connection 2 (Exclusive Owner - 32 bytes per IO-Link Port without Config)
The process data of the digital inputs and outputs have a fixed size of 276 Byte.
Output process data
The following table gives a description of the process data structure of the output process data.
Byte
Number
of bytes
Output process data
Description
1
1 byte
DO status
0: DO data not valid. Substitute values are used. 1-
255: DO data valid.
2
1 byte
Padding byte
Do not use
3 … 4
2 byte
DO data
Depends on setting for process data layout: pin-based or
port-based. See next table.
5
1 byte
IO-Link Port 1 Output enable
0: IO-Link Port 1 output data not valid. 1-
255: IO-Link Port 1 output data valid.
6
1 byte
Padding byte
Do not use
7 … 38
32 byte
IO-Link port 1 process output
data
IO-Link output data of the sensor/actor connected to Port 1.
For a description of the data, see manual of the
manufacturer of the used sensor/actor.
39
1 byte
IO-Link Port 2 Output enable
0: IO-Link Port 2 output data not valid. 1-
255: IO-Link Port 2 output data valid.
40
1 byte
Padding byte
Do not use
41 72
32 byte
IO-Link port 2 process output
data
IO-Link output data of the sensor/actor connected to Port 2.
For a description of the data, see manual of the
manufacturer of the used sensor/actor.
73
1 byte
IO-Link Port 3 Output enable
0: IO-Link Port 3 output data not valid. 1-
255: IO-Link Port 3 output data valid.
74
1 byte
Padding byte
Do not use
75 106
32 byte
IO-Link port 3 process output
data
IO-Link output data of the sensor/actor connected to Port 3.
For a description of the data, see manual of the
manufacturer of the used sensor/actor.
107
1 byte
IO-Link Port 4 Output enable
0: IO-Link Port 4 output data not valid. 1-
255: IO-Link Port 4 output data valid.
108
1 byte
Padding byte
Do not use
109 … 140
32 byte
IO-Link port 4 process output
data
IO-Link output data of the sensor/actor connected to Port 4.
For a description of the data, see manual of the
manufacturer of the used sensor/actor.
141
1 byte
IO-Link Port 5 Output enable
0: IO-Link Port 5 output data not valid. 1-
255: IO-Link Port 5 output data valid.
142
1 byte
Padding byte
Do not use
143 … 174
32 byte
IO-Link port 5 process output
data
IO-Link output data of the sensor/actor connected to Port 5.
For a description of the data, see manual of the
manufacturer of the used sensor/actor.
175
1 byte
IO-Link Port 6 Output enable
0: IO-Link Port 6 output data not valid. 1-
255: IO-Link Port 6 output data valid.