309 272 01 GB LUNA LUNA 120 top2 0 Installation and operating instructions Twilight switch 6 12 18 24 LUNA 120 top2 120 0 100 120 0 200 2 MENU OK Lux 2000 1 2 D GB F I 1 E P 8mm 0,5mm 2 2,5mm 2600 W 16A-10AX 250V~ 220-240V~ 230-240V~ 50-60Hz R10a Ò30T 2 3 NL PL LUNA 120 top2 Correct connection required for smooth zero crossing switch operation (see connection diagram)!
Contents Basic safety instructions Display and keys/operating instructions Overview of menu selection Connection/installation Connection/installation of light sensor Initial start-up Set lux values Menu item LIGHT Set delay Menu item PROGRAM Set switching time Menu item MANUAL Manual and permanent switching Menu item OPTIONS Enter PIN code OBELISK top2 memory card Technical data Service address/Hotline 2 3 4 5 6 7 8 9 10 11 12 13 13 14 14
Basic advice GB WARNING Danger of death through electric shock or fire! Installation should only be carried out by a professional electrician! • The device is designed for installation on DIN top hat rails (in accordance with EN 50022) • Power reserve (10 years) is reduced if memory card is inserted (in battery operation) • OBELISK top2 memory card: Avoid mechanical stress or contamination caused by other storage/ Transport vermeiden (available if required) Designated use • The digital twilight switch i
Screen display and keys Programmed ON switching times 0 6 12 18 Operating instructions 1. Read text line 24 Flashing text/symbol represents query Date display Time display Channel status ON OFF Days of the week from 1 to 7 2.
Overview of menu selection GB MENU 19 10 08 OFF 9:40 LIGHT PROGRAM TIME/DATE MANUAL OPTIONS END 46 ON DELAY ON DELAY END TIME FREE 56 PERMANENT ON DATE NEW VIEW PERMANENT OFF SUMMER-WINTER CHANGE DELETE END MANUAL ON WEEKDAY DATE FORMAT DATEFORMAT END TIMER HOLIDAY END OPERATING HOURS METER LCD ILLUMINATION LANGUAGE PIN FACTORYSETTINGS INFO END 5
Connection/installation WARNING Warning, danger of death through electric shock! Must be installed by a professional electrician! 45° cable Connect power source! Cover or shield any adjacent live components live components. Spring screwless terminal Ensure device cannot be switched on! Check power supply is disconnected! Spring Earth and bypass! Connect cable Strip cable by 8 mm (max. 9). Insert cable at 45° in the open terminal (2 cables per terminal position possible).
Connection/installation of light sensor GB Take length of connection cable into account max. 100 m 2 x 1,5 mm2, max. 50 m 2 x 0,75 mm2 Avoid running sensor wiring wiring parallel to mains power cables. 0,5–2,5 mm2, strip cable by 10 mm (max. 11 mm).
Initial start-up Set language, date, time as well as summer/ winter time GERMAN KEEP PROGRAM DATE FORMAT YEAR MONTH Press required key and display follows on screen (see fig).
Set lux values GB The twilight switch with external light sensor controls lighting equipment for streets, stairways, enrances etc. 0 6 12 18 24 LUNA 120 top2 Set desired range from I-V with a screw tab a screwdriver on the potentiometer setting (see fig). The red LED lights up as soon as the set Lux value falls below the ambient brightness level.
Set delay An on/off delay of 1 minute is preset to avoid faulty operation caused by lightning, car headlights etc. When the delay ends the channel status will flash ON/OFF. LIGHT ON DELAY MINUTE SECONDS Press MENU (see fig.).
Set switching time GB (e.g. with a night switch off at theweekend 23:00–05:00 Uhr) ok There are 56 available memory cells. ok NEW VIEW NIGHTSWITCH HOUR CHANGE MINUTE DELETE MONDAY END LASTS UNTIL COPY same switching time for several days = block Press MENU (see fig.).
Manual and permanent switching Manual and permanent switching can be set using the menu in MANUAL or (in the automatic screen) by key combination (see fig). Manual control Reversing the channel status to the next automatic or programmed switching. ok Channel C1 Activate manual switching Briefly press both keys simultaneously. Activate permanent switching Simultaneously press both keys for 2 seconds. Cancelling manual/permanent switching Press both keys simultaneously.
Enter PIN code OBELISK top2 memory card The PIN-Code is set via the menu in OPTIONS (see picture). If you have forgotten the PIN please call the Theben Hotline. Using memory card Insert memory card in the timer. Request savedswitch timings, read to/from the timer or start Obelisk program. Remove OBELISK top2 memory card (no. 907 0 404) after programming etc. and store in cover.
Technical data Nominal voltage: 220–240 V~, +10 %/-15 % Frequency: 50–60 Hz Brightness range: 2–2.000 lx On/off switch delay: 0–59 min Power consumption: type 3 VA Switching output: phase-independent (zero-crossover switching) Contact: two way switch Contact material: AgSnO2 Switching capacity: 16 A/250 V~ cos ϕ = 1 10 A/250 V~ cos ϕ = 0,6 Fluorescent lamps: 10 AX Switching capacity min.