Manual

Weathersafe Extreme
Installation and Operating
Instructions
IP66 Products covered by
these instructions
TGVL01 One gang two way switch 10AX
TGVL02 Two gang two way switch 10AX
TGVL03 One gang bell push
TGVL05 One gang double pole switch 20A
WXT101 One gang socket switched 13A
WXT201 Two gang socket switched 13A
WXT104 One gang RCD spur
WXT204 Two gang RCD protected socket
13A (passive/latching)
WXT205 Two gang RCD protected socket
13A (active/non-latching)
WXT203 Combined timer and socket
WXT103 One gang switched fused spur 13A
General
Please note that all instructions are to be left with the
customer after installation.
The Weathersafe Extreme range is manufactured from
tough, durable thermoplastic, and is intended for use in
an outdoor environment, or one in which the protection
provided by the Weathersafe Extreme range is required.
All the products are rated IP66, for protection against
water and dust. All Weathersafe Extreme products need
to be fitted with waterproof cable and conduit entries to
maintain their IP rating once installed.
The weather Extreme range complies with the following
standards.
• IP66rating:BSEN60529
• Socketoutlets:BS1363
• RCDunits:BS7288
• Fusedconnectionunits:BS1363
• Switches:BSEN60669
• Allproductsintherangecomplywiththelow
voltagedirectiveLV72/23/EECandwhere
relevanttheEMCdirective89/336/EEC
Voltage:230VAC50Hz
Operatingtemperaturerange:-5°to55°C
Installation instructions
• Theseproductsshouldbeinstalledbyacompetent
person (e.g. qualified electrician) in accordance with
these instructions and in compliance with the
appropriate clauses of the current edition if the IEE
wiringandbuildingregulations.Socketsshouldbe
connected via a suitable RCD device.
• Disconnectthemainselectricitysupply
before installing.
• TheWeathersafeExtremerangeisdesignedtobe
mounted on a vertical flat surface, with socket outlets
not more than 1 metre above the ground.
• Therearboxshallbemountedonthewallusingno.8
wood screws and wall plugs if necessary (see fig. 1).
• Ifthemountingsurfaceisunevenuseasheetof
marine ply as a base plate then fit the rear box to it.
Fig. 1
RearBox(double)
If conduit is to be used then please follow the
instructionsbelow:
• Thedrainfeaturemustbedrilledoutusing
a5mmdrilliftoporsideentryconduitisused.
Opening this drain hole will reduce the IP rating
of the product. Remember – open out the lower
drain feature only and only if required by
conduit entry being used.
• Ifbottomentryconduitisused,theremustbe
adequate drainage from the lowest point of
the conduit.
• Therelevantcableentryknockoutshould
be carefully removed by scoring the groove
around the knockout with a sharp knife and
then tapping it out with a small hammer.
A waterproof cable or conduit entry must
then be fitted in its place.
• Iftwocableentrypositionsareusedwith
metal conduit, then earth continuity between
the conduits must be maintained.
• Ensurethatthegasketiscorrectlytted,
and tighten the four screws (supplied) to fix
the front cover in place (see fig. 1). Do not
overtighten. Use of an electric screwdriver
is not recommended.
Operating Instructions
Fig. 2
Singleanddoubleboxes–sideviewofbottom.
• Thelidmaybeopenedbypressinginthetab(s)
on the front to release the snaps and then lifting
the lid (see fig.2).
• Plugsmaybeinsertedintothesocketsandthe
socket switches turned on.
• Thelidshouldthenbeclosedtomaintainthe
IP rating taking care to ensure that the cables
are aligned with the centre of the cable seals
(seeg.3).Finallyengagethesnaps(seeg.2)
by pulling out the tab(s) while maintaining
pressure to close the lid.
Fig. 3
RearBox(doublewith2gangRCDsockets)
Cleaning
• Careshouldbetakenwhencleaning
this product.
• Insidethelidshouldonlybewipedwitha
clean dry cloth.
• Theoutsidecanbecleanedwith
mild detergent.
• Solventbasedcleanersshouldnotbeused.
• Adviceshouldbesoughtbeforeinstallingthis
product in an environment where it is likely to
be subjected to chemicals, oils or solvents.
Weathersafe Extreme Products with
RCD’s (WXT104, WXT204, WXT205)
Always test the RCD before use.
To test: Ensure supply is connected
RESET – press the grey (blue for WXT205) button
marked Reset (R), the status indicator should show red.
TEST – press the red button marked Test (T),
status indicator should show black. This indicates
that the RCD has been tripped and power has been
disconnected from the outlet.
RESET – press the grey (blue for WXT205) button
marked Reset (R) again, the status indicator
should show red.
If all the above operations work satisfactorily, the RCD
is safe for use.
If the procedure is not completed satisfactorily do not
use the RCD and seek professional advice.
In applications such as hand driers it may not be
practical to expect each user to test before use. In this
case we suggest an appropriate person applies the test
routine twice a day.
4 x fixing holes for
no. 8 woodscrews
Drain feature,
use only lower if
required
Front cover
fixing holes
Cable aligned with
centre of seals
Status indicator
T
R
Push here and lift up
Snaps
Snaps