309563 03 TR 635 top2 TR TR 635 top2 TR 636 top2 6350100 6360100 Installation and operating instructions Digital time switch with weekly program D GB F I E NL 0 MENU 6 GB 12 18 24 OK TR 635 top2 Connection of different external wires is permitted
Contents Basic advice Screen and keys Operating instructions Overview of menu selection Connection/installation Initial start-up Reset 3 4 4 5 6 8 8 Menu item PROGRAM Set switching time Change/request switching time Delete switching time Pulse programming Cycle programming 9 11 11 12 13 Menu item MANUAL Manual and permanent switching 14 2 Menu item OPTIONS PIN code setting 14 OBELISK top2 memory card Service address/Hotline Technical data 15 15 16
Basic safety instructions GB WARNING Danger of death through electric shock or fire! Installation should only be carried out by a qualified electrician! • The device is intended for wall and front panel installation • Corresponds to type 1 BSTU in accordance with IEC/EN 60730-2-7 • Power reserve (10 years) is reduced if memory card is inserted (in battery operation) Designated use • The time switch can be used for lighting, bell systems, ventilation etc.
Screen display and keys Operating instructions Programmed switch times Date display C1 Channel status ON = On OFF = Off C2 C3 C4 1. Read text line Flashing text/symbol represents query Date display OK ESC Days of the week from 1 to 7 2.
Overview of menu selection GB MENU 19 05 11 ON 9:40 PROGRAM TIME/DATE MANUAL OPTIONS END 46 NEW TIME VIEW PERMANENT ON DATE CHANGE PERMANENT OF SUMMER-WINTER DELETE DAY OF THE WEEK END DATE FORMAT MANUAL ON TIMER HOLIDAY TIME FORMAT RANDOM END END OPERATING HOURS LCD-ILLUMINATION LANGUAGE PIN FACTORYSETTINGS INFO END 5
Connection WARNING Warning, danger of death through electric shock! Must be installed by qualified electrician! Disconnect power source. Cover or shield any adjacent live components. Ensure device cannot be switched on! Check power supply is disconnected. Earth and bypass.
Installation GB Distributor installation (wall) – for installation on DIN top hat rails (in accordance with EN 60715) with accessories (9070071) 907 0 071 Front panel installation – for installation in front frame and transparent cover (in accordance with DIN 43700) 7
Initial start-up Set date, time and summer/ winter time rule Press required key and display follows on screen (see figure). DEUTSCH RETAIN PROGRAMS DELETE PROGRAMS FORME DATE YEAR MONTH DAY FORM TIME HOUR RESET Press the 4 buttons simultaneously. You can choose between RETAIN PROGRAMS and DELETE PROGRAMS.
PROGRAM GB Program switching time Example: Switch on sports hall lighting from Mon–Fri, 7:30 to 12:00 hrs Press MENU. PROGRAM is displayed. Confirm by pressing OK. NEW is displayed. Confirm by pressing OK. SWITCHING TIME is displayed. Confirm by pressing OK. Select ON (for switch-on times). Confirm by pressing OK. The display shows HOUR. Use the + or – keys to enter hour, minute, (07:30) and confirm by pressing OK. MONDAY is displayed. Confirm by pressing OK. COPY is displayed.
MENU PROGRAM NEW SWITCH TIME PULSE CYCLE END ON HOUR ON 7.30 MINUTE MONDAY COPY TUESDAY WEDNESDAY SAVE ADD TUESDAY ... SAVE 10 84 memory locations are available.
Request/change/delete switching time Press MENU. PROGRAM is displayed. Confirm by pressing OK. NEW is displayed. Use to select CHECK. Confirm by pressing OK. Confirm SWITCH TIME by pressing OK. The first of the entered switching times is displayed. Confirm by pressing OK. NEXT is displayed. MENU PROGRAM NEW CHECK MODIFY DELETE SWITCH TIME MONDAY NEXT TUESDAY ...
Pulse time programming Example: Switch on pause signal on Monday 8:05 hrs for 5 sec 12 Press MENU. PROGRAM is displayed. Confirm by pressing OK. NEW is displayed. Confirm by pressing OK. SWITCH TIME is displayed. Select PULSE by pressing u. Confirm by pressing OK. ON is displayed. Confirm by pressing OK. The display shows HOUR. Use the + or – keys to enter hour, minute, second (8:05) and confirm by pressing OK. PULSE LENGTH is displayed.
Cycle time programming GB In addition to switch-on and switch-off times (switching time) and short time pulses (pulse) cycle times (cycle) can also be programmed. The pulse length (+ pulse pause) is limited to 17 hrs, 59 min, 59 sec • Cycle times refers to cyclically repetitive time functions such as fan controls, urinal rinses etc. Example: Switch on water rinsing Monday from 8:00 to 20:30 hrs every 15 min for 20 sec (8:0000–8:0020 On; 8:1500–8:1520 On; 8:3000–8:3020 On etc.
Manual and permanent switching Manual and permanent switching can be set using the menu in MANUAL or (in the automatic screen) by key combination (see fig.). Enter PIN code The PIN code can be set using the OPTIONS menu item (see fig.). If you forget the PIN call the Theben hotline. ok OPTIONS OPERATING HOUR Activate manual switching Briefly press both keys simultaneously. Activate permanent switching Simultaneously press both keys for 2 seconds.
OBELISK top2 memory card Serviceadresse/Hotline Use memory card Service address Insert memory card in the time switch. Read / read out saved switching times and device settings in the time switch or start Obelisk program. Remove memory card OBELISK top2 (No. 9070404) after copying. Avoid mechanical stress or dirtying with other storage/transport methods. GB Theben AG Hohenbergstr.
Technical data • Operating voltage: 230–240 V~, +10 %/-15 % • Frequency: 50–60 Hz • Power consumption: 0,8 W (TR 635 top2), 0,9 W (TR 636 top2) • Standby: 0,9 W (TR 635 top2), 1,1 W (TR 636 top2) • Switch output: switching of choice of external wires is permitted • Contact: two way switch • Gap: <3 mm (µ) • Contact material: AgSnO2 • Max switching capacity: TR 635 top2: 16 A, 250 V~, cos ϕ = 1 10 A, 250 V~, cos ϕ = 0,6 TR 636 top2: 6 A, 250 V~, cos ϕ = 1 6 A, 250 V~, cos ϕ = 0,6 • M