ADVANCED TECHNICAL MANUAL ACC1: Small System Control Console
ACC1: Small System Control Console ADVANCED TECHNICAL MANUAL Ta b l e of Contents Safety Precautions...................................................................................3 Overview..........................................................................................4 Specifications........................................................................4 Installation.....................................................................................5 Control Console Operation............
ACC1: Small System Control Console ADVANCED TECHNICAL MANUAL SAFETY PRECAUTIONS Please read and save the following important safety information regarding the ACC1 prior to unit operation.
ACC1: Small System Control Console ADVANCED TECHNICAL MANUAL OVERVIEW The Titus Control Console combines intelligent speed control with industry standard MODBUS® networking. The versatile design allows control of an array of Titus fan filter units with the installed universal control cards. The console combines a user interface with MODBUS master capability so no additional networking components are needed and no MODBUS knowledge is necessary to install a network.
ACC1: Small System Control Console ADVANCED TECHNICAL MANUAL INSTALLATION The Titus Control Systems are engineered for easy installation. However, testing either before permanent installation or as the system is installed is strongly recommended. The control console can be wall mounted in the cleanroom or at a remote location; however, the maximum recommended distance from the beginning to the end of the daisy chain should not exceed 800 linear feet.
ACC1: Small System Control Console ADVANCED TECHNICAL MANUAL INSTALLATION Elevation and Dimensions Installation Template 3.5” (89mm) 7.
ACC1: Small System Control Console ADVANCED TECHNICAL MANUAL 6.35±0.3 INSTALLATION 17±1 74±2 Control Console Power Connections The control console can be powered a plug-in style wall adapter, or a dedicated circuit board. 1. Plug in wall adapter: P/N: 64114-001 2.
ACC1: Small System Control Console ADVANCED TECHNICAL MANUAL INSTALLATION Specifications • Output: 12VDC at 1 Amp • AC Input Range: 14-28VAC • DC Input Range: 18-40VDC • Fault Protected • Short-Circuit Protected • Internally Current-Limited to 1.2A Installation • LED Power Indication • Simple Connections • RJ45 for network • ¼ “ Quick Connect for Transformer • Open-frame PCB with Standoffs • 0-40°C Operating Temperature • Surge Protection for Power and Data Lines • Dimensions: 2.20”(56mm) x 3.
ACC1: Small System Control Console ADVANCED TECHNICAL MANUAL Control Console Operation Front Panel Features Address Display Addresses 1 – 99 are displayed as ‘01’ – ‘99’ in the address display Address 100 is displayed as alternating ‘1’ and ‘00’ Addresses 101 and above are displayed as alternating ‘1’ and ‘01’ – ‘25’ Set Point Display Set point is displayed as a percentage of motor speed; ‘00’ – ‘99’ and ‘ON’ = 100% SELECTED ADDRESS ROTATE TO SELECT UNIT OR OPTION MENU PUSH TO ENTER OPTION MENU STATUS O
ACC1: Small System Control Console ADVANCED TECHNICAL MANUAL Control Console Operation Standby/Monitor Mode The control console immediately enters standby monitor mode at the conclusion of power-on scanning. The control console remains in standby monitor mode until one of the two dials are rotated. If the dials are not adjusted for a period of 30 seconds, the control console will revert to standby monitor mode.
ACC1: Small System Control Console ADVANCED TECHNICAL MANUAL Control Console Operation Option Mode To enter options mode, rotate select dial counter-clockwise until ‘OP’ is displayed in the Address Display. Then press the Select Dial to activate options mode.
ACC1: Small System Control Console ADVANCED TECHNICAL MANUAL Access Level Pass Code A1 A2 12 88 25 75 A3 49 51 A4 N/A Description Operator can adjust configuration settings. Operator can use all functions for monitoring and control. Operator can monitor and adjust high/low settings. Operator can only monitor status of the network.