Commissioning functions
Box options
16
Box options The box options set up the controller for the specific mechanical installation of
the VAV terminal unit. Setting the box options requires entering the Level 2
password which is described in the topic Enter the commissioning mode
on
page 14.
Procedure to set the box functions
Procedure Steps STE display
Starting display 1. Start at the temperature display.
2. Enter the Level 2 password. The
display changes to the COMM.
Select the box
settings display.
1. From the COMM display, press the
or buttons to show the CNFG
display.
2. Press the button to select the CNFG
options. The display changes to
STPT.
3. Press the or buttons to change
the display to BOX.
4. Press the button to select BOX.
Set the primary
VAV termina l unit
K-factor.
1. Press the or buttons to set the
primary K-factor.
2. Press the button to save the entry
and advance to the next function.
Set the secondary
VAV termina l unit
K-factor.
1. Press the or buttons to set the
secondary K-factor.
2. Press the button to save the entry
and advance to the next function.
72
12S1
PSW2
OOOO
Set
Point
Set
Point
COMM
CNFG
STPT
BOX
Set
Point
9O4
PKFT
Set
Point
9O4
SKFT