User Manual

INSTALLATION
VENT SYSTEM TERMINATION
Before installing Power Venter determine location of vent system termination.
TOOLS REQUIRED
• Saber Saw or Cement Drill • Drill • 1/8” and 1/4” Drill Bits
• Wood or Masonry Chisel • Blade Screwdriver or 1/4” Nut Driver • Wire Cutter/Stripper
NOTE: Termination of a Side Wall Vent System with a device other than the Tjernlund VH1 Series Vent Hood could affect system
performance and result in a possible safety hazard. Consult V
ent Hood instructions for complete installation details.
VENT HOOD TERMINATION CODE REQUIREMENTS FOR U.S. INSTALLATIONS
If possible, locate the Vent Hood on a wall that does not face the direction of prevailing winds. This will diminish the possi-
bility of appliance interruption during periods of extreme winds and prevent oil odors caused by backdrafts.
If possible, locate the Vent Hood no closer than 3 feet from an inside corner of an L-shaped structure.
Terminate the vent system so that proper minimum clearances are maintained as cited in the latest edition of the National Fuel Gas
Code (NFPA # 54) and the latest edition of NFPA #211, or as follows:
Not be less than 7 feet above grade when located adjacent to public walk ways.
At least 3 feet above any forced air inlet located within 10 feet.
At least 4 feet below, 4 feet horizontally from or 1 foot above any door, window or gravity air inlet into any building.
At least 12 inches above grade.
So that the flue gases are not directed so as to jeopardize people, overheat combustible structures or enter buildings, and
Not less than 2 feet from an adjacent building.
6
For oil installations do not terminate HS-Series Power Venters on vinyl siding because temperatures can easily exceed 150
0
F.
The SideShot® is the only Tjernlund Power Venter recommended for termination on vinyl siding when using oil.
P1 & P2 PRE-CYCLE FAN PROVER STATUS CHECK
The Pre-Cycle Prover Status Check is activated from the factory. When activated the UC1
Universal Control checks across P1 & P2 safety circuit (Venter Fan Prover) to verify that the Fan
Prover switch is “Open” upon a call for heat and not stuck “Closed”.
Pre-Cycle
Prover Status
Check Activated
9