FPS SERIES 1000W In 1U Front End Power Supplies INSTRUCTION MANUAL This Manual Cover Models: FPS1000-12 FPS1000-24 FPS1000-32 FPS1000-48 FPS-S1U 19” Rack Single Output FPS-T1U 19” Rack Triple Output DWG NO: IA599-04-02-A
FPS1000 SERIES INSTRUCTION MANUAL DWG NO: IA599-04-02 A
TABLE OF CONTENTS Warranty .................................................................................................................................Pg. 1 FPS1000, FPS-S1U and FPS-T1U rack Safety instructions ................................................. Pg. 2 FPS1000 Power Supply Chapter 1: FPS1000 Series Specifications ............................................................................ Pg. 4 Chapter 2: FPS1000 Series Outline drawings ...................................................
FPS1000 Instruction Manual WARRANTY This Densei-Lambda product is warranted against defects in materials and workmanship for a period of two years from date of shipment. During the warranty period , Densei-Lambda will, at it's option, either repair or replace products which prove to be defective. LIMITATION OF WARRANTY The warranty shall not apply to defects resulting from improper or inadequate usage or maintenance by the buyer, buyer supplied products or interfacing.
FPS1000 POWER SUPPLY AND FPS-S1U RACK SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS Operating personnel must not remove the FPS1000, FPS-S1U and the FPS-T1U cover. No internal adjustment or component replacement is allowed by non Densei-Lambda qualified service personnel. Never replace components with power cable connected. To avoid injuries,always disconnect power, discharge circuits and remove external voltage sources before touching components.
FPS1000 Instruction Manual ATTENTION: Risque de choc et de danger e'lectriques. Le de'branchement d'une seule alimenttation stabilise'e ne de'branche uniquement qu'un module "Alimentation Stabilise'e". Pour isoler completement le module en cause, il faut de'brancher toutes les alimentations stabilise'es. SAFETY SYMBOLS CAUTION Risk of Electrical Shock. Instruction manual symbol. The instrument will be marked with this symbol when it is necessary for the user to refer to the instruction manual.
CHAPTER 1 FPS1000 SERIES SPECIFICATIONS FPS1000 SERIES SPECIFICATIONS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 V Rated output voltage V Output voltage set point V Output voltage range A Maximum Output Current (Refer to Fig.
FPS1000 Instruction Manual CHAPTER 2 OUTLINE DRAWINGS 1.
2.
FPS1000 Instruction Manual CHAPTER 3 FPS1000 POWER SUPPLY INSTALLATION 3.1 GENERAL This chapter contains instructions for initial inspection, preparation for use and repackaging forshipment. NOTE FPS1000 power supplies series generate magnetic field which might affect the operation of other instruments. If your equipment is susceptible to magnetic fields, do not position it adjacent to the FPS1000 unit. 3.
3.7 CONNECTING THE LOAD WARNING Turn off the AC input power before making or changing any rear panel connection. Ensure that all connections are securely tightened before applying power. There is a potential shock hazard when using a power supply with a rated output greater than 40V. 3.7.1 Load Wiring. The following considerations should be made to select wiring for connecting the load to the power supply: * Current carrying capacity of the wire (refer to 3.7.2).
FPS1000 Instruction Manual 3.7.3 Noise and Impedance Effects To minimize the noise pickup or radiation, the load wires and remote sense wires should be twisted-pairs of the shortest possible length. Shielding of the sense leads may be necessary in high noise environments. Even if noise is not a concern, the load and remote sense wires should be twisted-pairs to reduce coupling between them, which might impact the stability of power supply. The sense leads should be separated from the power leads.
3.7.7 Input/Output connector information The FPS1000 series uses male connector PCIB24W9M400A1, Positronic connector. To mate FPS1000 series to the load circuitry, use female connector PCIB24W9F400A1-S1031, Positronic connector. Refer to Table 3-4 and to the Outline drawing in chapter 2 for the connector pinout description. Pin No 1,2,4 3,5,6 7 Function +V -V On/Off control Description Positive output voltage. Maximum current capacity: 24A/contact. Negative output voltage.
FPS1000 Instruction Manual CHAPTER 4 FUNCTIONS AND FEATURES 4.1 Input Voltage Range Input voltage is single phase 85~265Vac (47~63Hz). The power supply can be operated also with a DC input voltage, 120~330VDC but the safety approvals apply to the AC voltage only. Input voltage which is out of the specifications might cause damage to the unit. 4.2 Output voltage trimming The output voltage can be adjusted within the specifications via the V_Trim pin at the In/Out connector.
4.8 DC_OK signal An open collector output provides a low output voltage detection signal. The open collector output is on when the output voltage is higher than 80%+/-5% of the rated output voltage of the power supply. The open collector output is referenced to the Signals_Return potential and is isolated from the power supply +V and -V terminals The maximum sink current is 10mA and the maximum external voltage is 15V. Refer to Fig 4-3 for typical application.
FPS1000 Instruction Manual 4.11 Remote Sensing The Remote sensing compensates voltage drop on the load wiring. The maximum voltage drop on each wire is 1V, however, it is recommended to minimize the voltage drop on the load wires to improve the response to load current changes. In case that the sensing wires are long, use separate twisted pair wires for the sensing and for the load wires to minimize noise pick-up.
CHAPTER 5 BASIC CONNECTIONS FOR OPERATION 5.1 Connecting single load, Local sensing Local sensing is suitable for applications where load regulation is not critical. Fig 5-1 shows recommended load and sensing connections for applications with a single load.
FPS1000 Instruction Manual 5.4 Multiple loads connection with distribution terminals If remotely located output distribution terminals are used, the power supply output terminals should be connected to the distribution terminals by a pair of twisted or shielded wires. Each load should be separately connected to the remote distribution terminals (see Fig 5-4). If remote sensing is required, the sensing wires should be connected to the distribution terminals or at the most critical load.
CHAPTER 6 PARALLEL AND SERIES OPERATION 6.1 Parallel operation Up to 8 FPS1000 units of the same output voltage rating can be connected in parallel. By connecting the CS signal between the paralleled units, automatic current balance is achieved, with +/-10% accuracy. Derate the total output current by 10% when using parallel operation to prevent overload condition. The built-in Oring diodes on the main output and the 12V Auxiliary output allow N+1 operation.
FPS1000 Instruction Manual 6.1.3 Signal Return bus at parallel operation The Signal Return of each paralleled unit can be connected together to form a common Signal Return bus. By this way, the control and monitoring signals of the paralleled units can be connected to the same control and monitoring circuitry. The Signal Return bus can be connected to the -V or -S or +V or -S or float. Fig 6-3 shows typical connection of the Signal Return at parallel operation.
6.2 Series operation Two units can be seriesly connected to increase the output voltage or to create a bipolar voltage source. It is recommended to connect diodes in parallel with each output to prevent reverse voltage in case of failure in one of the power supplies. Each diode should be rated to at least the power supply rated output voltage and output current. Refer to Fig 6-5 and 6-6 for typical lseries connection of power supplies. Series connection for increased output voltage.
FPS1000 Instruction Manual CHAPTER 7 I2C BUS INTERFACE OPTION 7.1 Introduction The I2C interface option includes facilities to monitor operating parameters of the power supply. The parameters are then transferred to the host PC if demanded, over a standard I2C bus. The following data can be monitored for the individual units connected to the I2C bus: 1. Status of the unit. 2. Actual output voltage, output current and internal temperature of the unit. 3.
7.3 Block diagram of the I2C option Refer to Fig 7-1 for description of the I2C block diagram and for typical application. Output Fail OTP Temperature Alarm Fan Fail AC Input Fail A0 A1 A2 REGISTER Output voltage A0 A1 A2 Output current Temperature ADC A0 A1 A2 A0 A1 A2 EEPROM Serial CLOCK Fig 7-1: I2C option bloack diagram Serial DATA 7.4 Operation and functions 7.4.1. Digital status Digital status functions are provided by a PCF8574, 8-bit Register.
FPS1000 Instruction Manual 7.4.3 Analog functions Analog functions are provided by a single PCF8591, 4-channel 8-bit A/D converter. When this device is read by the serial buscontroller it provides an 8-bit word with the following information: Channel 1: Output voltage, channel 2: Output current, channel 3: Internal temperature.
7.5.3 Internal temperature measurement The internal ambient temperature is measured to provide information of the safe operation of the power supply. The internal ambient temperature is usually higher than the power supply air intake temperature due to internal power dissipation. As the power dissipation varies with the load, the internal ambient temperature increases with the load. Refer to Fig 7-2 for typical internal temperature rise above the air intake temperature versus the load. Internal temp.
FPS1000 Instruction Manual CHAPTER 8 FPS1000 MAINTENANCE 8.1 Introduction This chapter contains information about maintenance, calibration and troubleshooting of the FPS1000 power supply. 8.2 Units under warranty Units requiring repairs during the warranty period should be returned to Densei-Lambda authorized service office. Unauthorized repairs performed by other than the authorized service facilities may void the warranty. 8.
FPS-S1U 19” Rack Single Output 24
FPS-S1U Instruction Manual CHAPTER 9 FPS-S1U RACK SPECIFICATIONS 1 Number of power supply modules (*1) --- Maximum 3 x FPS1000 modules of the same output voltage rating. 2 Maximum output power (*2) W 3000 3 Input voltage / frequency range (*3) --- 85~265Vac continuous, 47~63Hz, Single phase 4 Maximum input current (at 100/200Vac) A 12.0/6.0 for each FPS1000 unit installed 5 AC input connector --- FPS-S1U :IEC inlet for each power supply module .
CHAPTER 10 FPS-S1U RACK INSTALLATION 10.1 GENERAL This chapter contains instructions for initial inspection, preparation for use and repackaging for shipment. In some sections in this chapter, where the instructions for the FPS-S1U and the FPS1000 are identical, a reference to a section describing the FPS1000 will be given. 10.2 PREPARATION FOR USE Table 10-1 below describes the basic setup procedure. Follow the instructions in Table 10-1 in the sequence given to prepare the FPS-S1U rack for use.
FPS-S1U Instruction Manual 10.7.3 Making the load connections WARNING ! Hazardous voltages may exist at the outputs and the load connections when using a power supply with a rated output greater than 40V. To protect personnel against accidental contact with hazardous voltages, ensure that the load and it's connections has no accessible live parts. Ensure that the load wiring insulation rating is greater than or equal to the maximum output voltage of the power supply.
10.7.5 Control and monitoring signals connector 9 CS Current sharing signal. When FPS-S1U racks are connected in parallel, the CS pins of the units should be connected to allow current balance between units. 10 V_TRIM_C Connection for output voltage trimming of FPS1000 unit "C". The voltage can be trimmed within its range specifications. 11 SIGNAL_RETURN Return for the following control and supervisory signals: On/Off, DC_OK, Over_temperature Alarm, AC_Fail, Auxiliary 12V supply.
FPS-S1U Instruction Manual 10.7.6 Modules location Up to three FPS1000 modules of the same output voltage rating can be plugged into an FPS-S1U rack. Refer to Fig 10-2 for the modules location. PS MODULE “A” PS MODULE “B” Air flow direction Front side see note 1 PS MODULE “C” Fig 10-2: FPS1000 modules location Note 1: Forced air cooling allow minimum 50mm of unrestricted air space at the rear of the unit. Do not obsruct air flow to the unit front panel. 10.7.
CHAPTER 11 FPS-S1U AND FPS-S1U/P OUTLINE DRAWINGS 11.
FPS-S1U Instruction Manual 11.
CHAPTER 12 BASIC CONNECTIONS FOR OPERATION FPS-S1U RACK 12.1 Connecting single load, Local sensing Local sensing is suitable for applications where load regulation is not critical. Fig 12-1 shows recommended load and sensing connections for applications with a single load.
FPS-S1U Instruction Manual 12.4 On/Off control Fig 12-4 shows typical connection for individual On/Off control of each installed FPS1000 unit. The On/Off control signal is applied to the DB25 connector located at the rear panel (refer to sec. 10.7.5). When it is desired to control all the installed units simultaneously, it is possible to connect the On/Off control as shown in Fig 12-5.
CHAPTER 13 PARALLEL AND SERIES OPERATION 13.1 Parallel operation Up to 3 FPS-S1U racks with up to 8 FPS1000 installed units of the same output voltage rating can be connected in parallel. The built-in Oring diodes on the main output and on the +12V auxiliary voltage in each FPS1000 unit allow N+1 operation. By connecting the CS signal between the paralleled units, automatic current balance is achieved, with +/-10% accuracy.
FPS-S1U Instruction Manual 13.1.2 Output voltage trimming at parallel operation The output voltage of the units connected in parallel can be made by a single trimmer or resistive divider. 7 V_TRIM 1 A, B, C 10 FPS-S1U # 1 CS 9 SIG. RTN 11 ON/ OFF ON/ ON/ OFF OFF A B 9 SIG. RTN 11 V_TRIM V_TRIM 7 V_TRIM 1 V_TRIM A, B, C 10 ON/ OFF ON/ ON/ OFF OFF A FPS-S1U with FPS1000-12 installed: 2 R2=0.0324*V out -1.1298*Vout+9.
13.1.4 Remote On/Off control at parallel operation The paralleled racks can be turned On or Off via a single On/Off control. Refer to Fig 13-5 for typical application. The Signal Return function of all the paralleled racks should be connected together to create a common Signal Return bus. The Signal Return bus may be connected to the -V or the +V potential or floated. In any case do not connect the Signal Return bus to different potentials. FPS-S1U #1 ON/OFF A, B, C 5, 15, 25 SIG. RETURN 2.
FPS-S1U Instruction Manual CHAPTER 14 FPS-S1U I2C BUS INTERFACE OPTION 14.1 Introduction The FPS-S1U rack provides access to the I2C Bus interface in each installed FPS1000/S unit via the rear panel DB25 female connector located at the rear panel. The Clock is connected to pin 20 and the Data is connected to pin 21. The specifications of the I2C of the FPS1000/S power supplies are kept when they are installed in the FPS-S1U rack. Refer to Chapter 7 for the specifications and all operating details. 14.
CHAPTER 15 FPS-S1U MAINTENANCE 15.1 Introduction This chapter contains information about maintenance, calibration and troubleshooting of the FPS-S1U rack. 15.2 Units under warranty Units requiring repairs during the warranty period should be returned to Densei-Lambda authorized service office. Unauthorized repairs performed by other than the authorized service facilities may void the warranty. 15.3 Periodic maintenance No routine maintenance of the FPS-S1U rack is required except for periodic cleaning.
FPS-T1U 19” Rack Triple Output 39
CHAPTER 16 FPS-T1U RACK SPECIFICATIONS 1 Number of power supply modules (*1) --- Maximum 3 x FPS1000 modules. 2 Maximum output power (*2) W 3000 3 Input voltage / frequency range (*3) --- 85~265Vac continuous, 47~63Hz, Single phase 4 Maximum input current (at 100/200Vac) A 12.0/6.0 for each FPS1000 unit installed 5 AC input connector --- FPS-T1U :IEC inlet for each power supply module . FPS-T1U/P :None 6 Output terminals --- Bus-bars.Refer to outline drawing.
FPS-T1U Instruction Manual CHAPTER 17 FPS-T1U RACK INSTALLATION 17.1 GENERAL This chapter contains instructions for initial inspection, preparation for use and repackaging for shipment. In some sections in this chapter, where the instructions for the FPS-T1U and the FPS1000 are identical, a reference to a section describing the FPS1000 will be given. 17.2 PREPARATION FOR USE Table 10-1 below describes the basic setup procedure.
17.7.3 Making the load connections ! WARNING Hazardous voltages may exist at the outputs and the load connections when using a power supply with a rated output greater than 40V. To protect personnel against accidental contact with hazardous voltages, ensure that the load and it's connections has no accessible live parts. Ensure that the load wiring insulation rating is greater than or equal to the maximum output voltage of the power supply.
FPS-T1U Instruction Manual 17.7.5 Rear Panel In/Out Connector Pins Function Description J1(A), J2(B), J3(C) Pin No Function Description 1 SDA (I2C) Serial Data used in the I2C interface option. Refer to the I2C interface description in the FPS1000 Instruction Manual. 2 SCL (I2C) Serial Clock used in the I2C interface option. Refer to the I2C interface description in the FPS1000 Instruction Manual.
17.7.6 Modules location Up to three FPS1000 modules can be plugged into an FPS-T1U rack. Refer to Fig 17-2 for the modules location. PS MODULE “A” PS MODULE “B” Air flow direction Front side see note 1 PS MODULE “C” Fig 17-2: FPS1000 modules location Note 1: Forced air cooling allow minimum 50mm of unrestricted air space at the rear of the unit. Do not obsruct air flow to the unit front panel. 17.7.7 Blank panels Each FPS-T1U rack is supplied with two blank panels in the package.
FPS-T1U Instruction Manual CHAPTER 18 FPS-T1U AND FPS-T1U/P OUTLINE DRAWINGS 18.
18.2 FPS-T1U/P Outline Drawing 11.
FPS-T1U Instruction Manual CHAPTER 19 BASIC CONNECTIONS FOR OPERATION FPS-T1U RACK 19.1 Connecting Single Load, Remote Sensing Remote sensing is used in cases where the load regulation is important at the load terminals. Use twisted or shielded wires to minimize noise pick-up. If shielded wires are used, the shield should be connected to the ground at one point, either the power supply side or the load. The optimal point for the shield ground should be determined by experimentation.
19.3 Output Voltag Trimming Fig 19-4 shows typical output voltage trimming connection for FPS1000 unit ‘A’ inside the rack Units ‘B’ and ‘C’ connections - Refer to 17.7.5 FPS1000-12: 2 R2=0.0324*V out -1.1298*Vout+9.9342 R1(KΩ)=5(KΩ)-R2(KΩ) J1(A) FPS-T1U +S FPS1000 Module A V_TRIM -S J1(A)-8 J1(A)-6 J1(A)-7 R1 FPS1000-24: 2 R2=0.0785*V out -5.819*Vout+105.132 R1(KΩ)=20(KΩ)-R2(KΩ) R2 R1&R2:0.5W FPS-1000 Module B J2(B) FPS-1000 Module C J3(C) FPS1000-32: 2 R2=0.0463*V out -4.5805*Vout+109.
FPS-T1U Instruction Manual CHAPTER 20 PARALLEL AND SERIES OPERATION 20.1 Parallel operation Up to 3 x FPS-T1U racks with up to 8 x FPS1000 installed units of the same output voltage rating can be connected in parallel. The built-in Oring diodes on the main output and on the +12V auxiliary voltage in each FPS1000 unit allow N+1 operation. By connecting the CS signal between the paralleled units, automatic current balance is achieved, with +/-10% accuracy.
20.2 Series operation Up to three FPS1000 with the same output voltage rating can be connected in series to increase the output voltage or to create a bipolar voltage source. It is recommended to connect diodes in parallel with each output to prevent reverse voltage in case of failure in one of the power supplies. Each diode should be rated to at least the power supply rated output voltage and output current. Refer to Fig 20-3 for a typical series connection of power supplies.
FPS-T1U Instruction Manual CHAPTER 21 FPS-T1U I2C BUS INTERFACE OPTION 21.1 Introduction The FPS-T1U rack provides access to the I2C Bus interface in each installed FPS1000/S unit via the rear panel MOLEX female connector located at the rear panel. The Clock is connected to pin 2 and the Data is connected to pin 1. The specifications of the I2C of the FPS1000/S power supplies are kept when they are installed in the FPS-T1U rack. Refer to Chapter 7 for the specifications and all operating details. 21.
CHAPTER 22 FPS-T1U MAINTENANCE 22.1 Introduction This chapter contains information about maintenance, calibration and troubleshooting of the FPS-T1U rack. 22.2 Units under warranty Units requiring repairs during the warranty period should be returned to Densei-Lambda authorized service office. Unauthorized repairs performed by other than the authorized service facilities may void the warranty. 22.3 Periodic maintenance No routine maintenance of the FPS-T1U rack is required except for periodic cleaning.
Notes 53
Notes 56