7. MAKING EMERGENCY BROADCASTS
7.1. Initiating Emergency Broadcasts Manually
Under manual operation, the broadcast areas are selected and the broadcast is conducted using either a
microphone or the pre-recorded voice alarm messages stored in the FS-7000EV.
[Buttons and keys used for operation]
[FS-7000EV]
[FS-7000CP]
[FS-7010CP]
Emergency
Reset Button
Emergency
Activation Button
Evacuation Announcement
Indicator
Fire Indicator Evacuation
Announcement Button
Talk Switch
CP Microphone
Zone Selector Keys Zone Indicators
Zone Selector Keys Zone Indicators
Step 1. Press the Emergency activation button on the FS-7000EV.
The Fire indicator will light.
2-channel broadcast: Broadcasting is stopped in areas where priority broadcasts are underway.
BGM broadcasting continues.
1-channel broadcast: Broadcasting is stopped in all areas.
Step 2. Use the Zone selector keys on the FS-7000CP or FS-7010CP to select the broadcast areas.
The appropriate Zone indicators will illuminate.
2-channel broadcast: BGM broadcasting in the selected areas is stopped.