9.4.4. Connections
Connections of the Emergency Power Supply Panel DS-029B are classified into four methods a, b, c, and d
depending on the composition selected in the section "About the Emergency Supply Panel" on p. 8. Because
the operation and control sections are fundamental to the emergency broadcast system, any failure in their
operation will disable the function of the entire system. When two or more DS-029Bs are incorporated into the
system (connection methods c and d), the system's operating time can be extended by connecting all the
positive (+) and negative () REMOTE (left) terminals on all DS-029Bs in parallel. This permits all connected
batteries to be used as a backup power source for the operation and control sections.
Important: Be sure to connect the DS-029B's power source to the "UNSWITCHED" AC outlet located on the
JP-0410's rear panel.
Connection method a for the DS-029B
In this method, one battery (one DS-029B unit) is connected to supply power to both the operation/control
section and power amplifier panel.
PA-1230B's rear panel
DS-029B's rear panel
JP-0410's rear panel
Battery 1
NDC-2460
[Connection Example]
Rated output: 120 W
Battery composition: 6 Ah power is supplied to both operation/control section and power amplifier panel