User Manual

34
9.6. DC Power Supply Panel Connection
9.6.1. When the DC power supply panel is not required (i.e. when you can do with the junction panel's
internal power supply)....
The power capacity of the Junction Panel's (JP-0410) internal power supply is 2 A in maximum output current.
Note the total current of connected components and external equipment. If their total current exceeds 2 A, the
power supply must be expanded. If not exceeding 2 A, use the junction panel with a jumper wire connected
between 24V IN and OUT terminals. (The jumper wire is connected at the factory.)
JP-0410's rear-mounted
terminal block
Jumper wire
Jumper wire
Rack mounted components
(Operation on 24 VDC)
Emergency power supply
DS-029B
OUT
IN
Internal circuit
Internal power supply
JP-0410
Emergency remote control unit
General remote control unit
Emergency cutoff 24 V
External equipment
Rack-mounted components (operation on 24 VDC)
Rack-connected external equipment (operation on 24 VDC)
Current Consumption
0.45 A
0.4 A
0.65 A
0.6 A
0.1 A
0.18 A
0.2 A
0.4 A
Model No.
JP-0410 (internal circuit)
JP-039-10
JP-039-20
EP-0510
EP-029-10
EP-029-20
PP-025B
MP-011
Component Name
Junction Panel
10-zone Expansion Junction Panel
20-zone Expansion Junction Panel
Integrated Control Panel
10-zone Expansion Operation Panel
20-zone Expansion Operation Panel
Pre-amplifier Panel
Monitor Panel
Current Consumption
0.3 A
0.1 A
0.18 A
0.13 A
0.13 A
Model No.
EP-059R
EP-029-10
EP-029-20
RM-1100
RM-1200
Component Name
Integrated Emergency Remote Control Panel
10-zone Expansion Operation Panel
20-zone Expansion Operation Panel
10-zone Remote Microphone
20-zone Remote Microphone