User Manual

35
9.6.2. When expanding the power supply for external equipment
Let us assume that one expansion power supply is added to the system solely to cover the shortage of power
to be supplied to external equipment as the result of connecting many external equipment or mounting many
components in the rack.
Note: Remove the jumper wire placed between the 24V IN and OUT terminals of the terminal block located on
the rear panel of the Junction Panel JP-0410.
Rack mounted components
(Operation on 24 VDC)
DS-029B
OUT
IN
Internal circuit
Internal power supply
Emergency power supply
Expansion power supply
JP-0410
Emergency remote control unit
General remote control unit
Emergency cutoff 24 V
External equipment
<DC power supply panel>
Two types of expansion power supplies (DC power supply panels) are made available depending on the
current capacity.
GND GND GND
DC24V DC24V Main power supply
IN OUT MAX10A
AD-031B's rear-mounted
terminal block
AD-011's rear-mounted terminal block
24 VDC OUT 24 VDC IN
AD-011: Maximum current 2.5 A
AD-031B: Maximum current 10 A
Connects to GND terminal of JP-0410's rear-mounted
terminal block.
Connects to DC24 V IN terminal of JP-0410's rear-
mounted terminal block.
Connects to DC24V IN terminal of JP-0410's rear-
mounted terminal block.
Connects to GND terminal of JP-0410's rear-mounted
terminal block.
9.6.3. When expanding the power supply for internal equipment
When many components are mounted in the rack, the power supply system needs to be divided using an
expansion power supply.
Memo
Leave a jumper wire connected between 24V IN and OUT terminals of the terminal block located on the rear
panel of the Junction Panel JP-0410.
Supply power to the Integrated Control Panel EP-0510 from the JP-0410.
Connect the output terminal of the Emergency Power Supply Panel DS-029B to the DC input terminal of the
expansion power supply.
Rack mounted components
(Operation on 24 VDC)
Rack mounted
components
(Operation
on 24 VDC)
DS-029B
OUT
IN
Internal circuit
Internal power supply
Emergency
power supply
Expansion
power supply
JP-0410
Emergency remote control unit
General remote control unit
Emergency cutoff 24V
<DC power supply panel>
External equipment