24 VDC
0.6 A
Composite audio signal tone (1st signal, 2nd signal, Warning Announcement,
Evacuation Announcement, False Alarm Announcement)
1st basement - 22nd floor, 1st basement - 5th floor, stairs, elevator, roof top,
penthouse, gymnasium, auditorium, and no floor.
Notes
Expandable to up to 330 zones (floors) by expanding the flash memory card
(option).
Additional expense is charged for writing into the flash memory card.
English
Interlock or all-zone interlock
Two-floor interlock or two-floor non-interlock
Warning Announcement Interlock or Warning Announcement Non-interlock
30 seconds - 15 minutes 30 seconds (set in 30-second units with the internal
DIP switches)
Off/0 - 15 minutes 30 seconds (set in 30-second units with the internal DIP
switches)
PA microphone (attachment) : 40 dBV, 600 , unbalanced, 4-pin jack
General pre-amplifier : 0 dBV, 600 , balanced, phone jack
Timer (time signal) : 0 dBV, 600 , unbalanced, phone jack
Attenuator-free audio input : 0 dBV, 600 , unbalanced, phone jack
Emergency/general output : 0 dBV, 15 , balanced, phone jack
10 individual zones + all zones, 5 groups (expandable to up to 330 individual
zones by expanding the EP-029)
Status: Voice alarm on, microphone announcement on,
Warning Announcement on, Evacuation Announcement on,
False Alarm Announcement on, abnormality in progress,
General Broadcast on, system check in progress
Output format: Open collector output, withstand voltage: 24 VDC,
current capacity: 0.1 A
Voice operation guide and screen display (30 characters x 4 lines)
3 W
Panel: ABS resin, black
Case: Zinc-plated steel plate (1 mm thick)
482 (w) x 221.4 (h) x 135.5 (d) mm
4.5 kg
Chime switch assembly x 1, balanced phone plug x 1, fuse (2 A) x 1,
balanced dual-plug cord x 1, PA microphone (uni-directional, dynamic type) x 1,
rack mounting screw x 4, name label (for individual zones) x 2,
name label (for zone group) x 1
49
15. SPECIFICATIONS OF THE MAIN RACK COMPONENTS
Integrated Control Panel EP-0510
Power Source
Current Consumption
Emergency Alarm
Fire Floor Information
Fire Floor Information
Language
Fire Alarm Interlock
Mode
Two-floor Interlock
Mode
Warning Announcement
Interlock
Evacuation
Announcement Interval
All-zone Broadcast
Interval
Input
Output
Output Control
Broadcast Status
Output
Function
Monitor Speaker
Finish
Dimensions
Weight
Accessories