In Connection diagram 2, attenuator-free broadcast can automatically be made using the digital
announcement machine, etc. when the attenuator-free broadcast switch is shorted. Determine broadcasting
lines by writing into the Integrated Control Panel EP-0510.
Notes
In this connection example, because power (24 VDC) is always supplied from the battery built in the
emergency power supply panel for power-failure general/attenuator-free broadcasts to the digital announcer,
etc. (even when the attenuator-free broadcast switch is not shorted), the battery is drained quicker than in
the example of Connection diagram 1. Use the battery having a sufficient current capacity.
The power-failure broadcast function is operated even when the AC power is supplied. In such cases, the
power-failure broadcast takes precedence over all other broadcasts.
When the AC power is supplied, 24 VDC is not output from the emergency power supply panel's control
terminal.
To automatically inspect the battery for power-failure general/attenuator-free broadcasts, connect the battery
check terminal and VOLT DOWN terminal in the same manner as the emergency power supply panel.
This applies to both connection examples of Connection diagrams 1 and 2.
Attenuator-free
broadcast switch
Attenuator-free input
24 VDC
(+)
(
-
)
Busy output
Output
Digital announcer, etc.
JP-0410
To EP-0510 attenuator-free
broadcast input
Emergency power supply panel for power-failure
general broadcast/attenuator-free broadcast
Connection diagram 2
To power amplifier 24 VDC