Installation Guide

FIXTURE RETROFIT INSTRUCTIONS
WARNING - To avoid shock or re hazard, turn o power to the xture at the
appropriate breaker or fuse panel.
STEP 1: Verify the voltage rang of the lamp (120VAC) matches the voltage of the
xture circuit.
STEP 2: Remove old uorescent lamps and remove the ballast cover.
STEP 3: Cut all wires aached to the ballast(s) as close to the ballast(s) as possible.
Leave the ballast(s) in place.
Note: TOGGLED lamps are powered from a single-end (designated with the product
label or markings) and require the use of non-shunted lampholders.
If the lampholders are shunted, replace them with the non-shunted lampholders
supplied with the lamp(s). See "Shunted Lampholder Replacement" below.
STEP 4: Connect one wire from each lampholder at one end of the xture to line
(black) and separately connect the other wire to neutral (white). At the opposite end
of the xture, cut all wires from the lampholders.
Note: Ensure the xture is and remains grounded aer the retrot process.
STEP 5: Reinstall any removed wiring covers and ballast covers.
STEP 6: Ax the included xture-modicaon label to the newly retroed xture. To indi-
cate which end is powered, place the label on the ballast cover nearest the powered end.
STEP 7: Install the new TOGGLED lamp(s). Be sure to install the lamp in the proper
orientaon (the end with the product labels/markings should be connected
to the AC wired lampholders).
SHUNTED LAMPHOLDER REPLACEMENT
STEP 1: Remove any brackets or covers holding the shunted lampholders in place.
STEP 2: Cut any wires aached to the shunted lampholders. Be careful to cut the wires
as close to the shunted lampholders as possible. You will need to reuse this wire.
STEP 3: Strip wires according to the strip gauge on the new lampholders. If a gauge is
not available, strip wires 3/8" [9.5mm].
STEP 4: Insert 1 wire on each side of each lampholder as indicated below.
STEP 5: Reinstall the lampholders and any removed covers or brackets.
This device complies with part 15 of the FCC rules. Operaon
is subject to the following two condions: (1) This device
may not cause harmful interference, and (2) this device must
accept any interference received, including interference that
may cause undesired operaon. Unauthorized changes or
modicaons to this device may result in a void in compli-
ance of part 15 of the FCC rules.
4XB9
LED RETROFIT CONVERSION: FOR USE ONLY WITH THE
PRODUCTS DESCRIBED AND INSTALLED IN ACCORDANCE
WITH THESE INSTALLATION INSTRUCTIONS PROVIDED
WITH THIS RETROFIT KIT.
Catalog
Number
Lamp
Length
Lamp Power Fixture Type Min. Fixture
Dimensions
Max. Qty.
Lamps
D416 48" 16W Recessed (IC)*
Surface*
24" x 48"
24" x 48"
4
4
* Lamps are rated for both open and closed xtures
Symptom Cause Remedy
No light from
LED tube(s)
when powered
on
LED Tube installed
backwards
Ensure lamp is installed with label nearest the wired (powered)
end of the xture
Fixture wired
improperly or
loose connecons
exist
Check wiring with schemac in provided installaon instrucons
Check wire-nuts for loose connecons
Check lampholder(s) at powered end of xture to ensure both
lamp pins are receiving 120VAC
Faulty LED tube Contact TOGGLED (1-844-864-4533)
Circuit breaker
detects a fault
condion when
light switch
turned on
Shunted Lam-
pholders installed
Replace exisng lampholders with included replacement
non-shunted lampholders. Follow above installaon instrucons.
Fixture wired
improperly
Check wiring with schemac in provided installaon instrucons
Check wire-nuts for loose connecons
Check lampholder(s) at powered end of xture to ensure both
lamp pins are receiving 120VAC
Only half of
the LED tube is
lighng up
Faulty LED tube Contact TOGGLED (1-844-864-4533)
All other issues Unknown Contact TOGGLED (1-844-864-4533)
TROUBLESHOOTING
Es
¡IMPORTANTE! ILos tubos de LED TOGGLED requieren la modicación del
cableado dentro de la luminaria uorescente existente. Siga las instrucciones
especícas a connuación. Si ene algún comentario o pregunta, no dude en
comunicarse con 1-844-TOGGLED.
ESTE KIT CONTIENE:
(1) Folleto de instrucciones de instalación
(1) Lámpara LED TOGGLED (D416)
(2) Tuercas conectoras de cable cercadas por la norma UL
(2) Portalámparas G13 cercado por la norma UL
(1) Equeta de modicación de luminaria
ADVERTENCIA – Riesgo de incendio o descarga eléctrica. La instalación del kit de
sistemas de iluminación con LED requiere el conocimiento de los sistemas eléctricos
para luminarias. Si usted no reúne las condiciones, no intente realizar ninguna
instalación. Comuníquese con un electricista cualicado.
ADVERTENCIA – Riesgo de incendio o descarga eléctrica. Instale este kit únicamente
en las luminarias que cuenten con las caracteríscas y dimensiones de estructura
que se muestran en los dibujos y/o fotograas.
No haga ni altere ningún oricio de los cableados o componentes eléctricos durante
la instalación del kit.
ADVERTENCIA – Para evitar la abrasión de los cables, no exponga el cableado a
bordes de chapas metálicas u otros objetos losos.
ADVERTENCIAPara evitar posibles incendios o descargas, no ulice este kit de sistemas
de iluminación en luminarias que posean portalámparas con derivación de dos clavijas.
ADVERTENCIA – Esta luminaria debe conectarse a erra e instalarse según los
códigos eléctricos nacionales y locales; la conexión e instalación debe realizarlas una
persona que conozca la estructura y el funcionamiento del producto, y los riesgos
involucrados.
Nota: Los portalámparas con derivación solo se encuentran en luminarias uorescentes
con balastos de encendido instantáneo. Los balastos de encendido instantáneo se pueden
idencar con la palabras “Instant Start” (encendido instantáneo) o con “I.S.” (E.I.)”. Esta
denominación puede ser un enunciado que pertenece al mismo balasto o puede estar
combinada con las indicaciones de las lámparas diseñadas para ulizar con el balasto, por
ejemplo, F40T12/IS. Para obtener más información, comuníquese con TOGGLED.
Los instaladores no deben desconectar los cables existentes de los terminales de los
portalámparas para realizar nuevas conexiones en los terminales de los portalámparas.
En lugar de ello, deben cortar los cables conductores de los portalámparas existentes
lejos del portalámparas y realizar las conexiones eléctricas nuevas a los cables
conductores de los portalámparas empleando los conectores correspondientes.
Este disposivo no está diseñado para que se lo ulice en salidas de emergencia.
Consulte el sio www.toggled.com/dim para determinar la compabilidad del
reductor de luz
164 Indusco Court
Troy, Michigan 48083-4641 USA
1-844-TOGGLED
support@toggled.com
toggled.com
TOGGLED is an company