TOHO ELECTRONICS INC. Program Controller TTM-339 Operation Manual Thank you for purchasing Toho Electronics’ TTM-339 series. Before using the products, thoroughly read this manual for a better understanding of them. Ensure to store this manual and use it whenever needed.
1.Precautions on the use of the products Ensure to read this manual before using the equipment. Take care to understand the following for the safe use of the equipment. Ensure this manual to be in hands of a person using the equipment. ★ Precautions on safety Alarms are defined and categorized into either one of four groups in this manual, depending on degrees of importance or risk in terms of the safe use of the equipment or prevention of accident or damage on the equipment.
Turn off the power supply before cleaning the equipment, and wipe it with a soft dry cloth. Do not use thinners, as they may cause deformation or discoloration of the equipment. The equipment may cause radio disturbances in domestic settings. User is required to take appropriate measure. Ensure to tighten terminal screws at specified torque. Insufficient tightening the screws may cause an electric shock or fire. Ensure to observe precautions listed in this manual for the use of the equipment.
2. Parts indication and Installation 2.1 Full panel face ③ ④ ⑤ ① PV ② PTN STP SV RUN EV1 EV3 TS1 TS3 AUTO AT TIME OUT EV2 EV4 TS2 TS4 MANU END C D B A RUN/STOP DSP.CHG D i g..MOVE AUTO/MAN RESET MODE ▽ △ E 2.2 F G H Segment display section No. Segment character Content ① PV (5 digits in the upper row) Displays PV, etc. ② SV (5 digits in the lower row) Displays SV, etc. Fixed to 0 during a stop. Displays “TIME” during a timer run.
2.4 Lamp display section Lamp character Content PTN Lights up while a pattern in display. STP Lights up while a step in display. RUN Lights up during a program run. OUT Lights up at the heating output ON. EV1 Lights up at occurrence of Event 1. EV2 Lights up at occurrence of Event 2. EV3 Lights up at occurrence of Event 3. EV4 Lights up at occurrence of Event 4. TS1 Lights up at Time Signal 1 ON. TS2 Lights up at Time Signal 2 ON. TS3 Lights up at Time Signal 3 ON.
2.7 Precautions on installation Warning Ensure to turn the power supply off before beginning removal or reinstallation of the equipment in order to prevent an electric shock or equipment failure. ★ Ambient temperature and humidity (the equipment to be used in the specified range as listed below) (1) Temperature range: 0 - 50 °C (2) Humidity range: 20 - 90% PH (no dew condensation allowed) (3) Installation gradient: Base plane ± 10 degrees ★ Do not install the equipment in the following places.
3.
The use of shielded wires is recommended. For Pt100 (resistance temperature detector), use identical wires of low lead resistance and no resistance difference among 3 wires. 4. Terms and Various Functions 4.1 Program run * The following number of steps is fixedly set, depending on the number of patterns. Pattern No. 1 2 3 4 5 6 Step No. 99 49 33 24 19 16 7 14 8 12 Pattern No. 9 10 11 12 13 14 15 Step No.
4.4 Wait function For the current step transferring to the next step, the next step does not begin if PV has not reached the wait zone (similarly, if PV has overreached) after the step time elapsed. However, if the wait time elapses, the next step begins at that point. The above operation is executed by selecting 0 to 4 for each step, or by setting value for 1 to 4. Selecting 0 indicates no function. In the case of [the wait zone setting = 0], in-a- wait is effective until PV goes beyond SV.
4.8 Time signal output At starting each step, the time signals 1 to 4 are turned on upon elapse of the time set on the ON delay timer. Then, the output is turned off upon elapse of the time set on the OFF delay timer. During the time signal output ON, corresponding lamps of TS1 to TS4 light up.
The step changes when the external contact open (OFF) changes to the external contact closed (ON) during a program run. 4.11.4 Patterns 1 to 4 DI A pattern is selected from 1 to 15, which are configured by combination of the external contacts 1 to 4 closed (ON) and open (OFF). No switchover of a pattern No. is possible during a run. If all external contacts 1 to 4 are open (OFF), choose the pattern No. selected in the pattern No. setting mode.
4.13.2 Operation amount current limiter The operation amount and current value are limited at each point obtained by dividing SLL to SLH into 10. At the operation amount limiter points 1 to 11, the operation amount resulted from calculation is limited.
Example: Assume the following for various settings and PV: PV = 120 C, operation amount limiter point 2 = 75.0%, current value limiter point 2 = 10.0 A, present operation amount = 60.0% and AHC = 1.0 A. If measured current valued = 15 A: Based on the relation [0 to present operation amount (60.0%) = 0.0 to measured current value (15.0 A)], the operation amount [current value limiter point 2 (10.0 A) - current limiter sensitivity (1.0 A)] is to be determined.
4.14.3-2 Primary/secondary control operation amount increase time Setting items: Primary/secondary control operation amount increase time: 0 to 3600 [second] (no function by setting at 0 [second]) Operation description: For a remote run, apply a limit on the operation amount such that the ratio of the operation amount to the calculated operation amount is from 0% at the start to 100% at the setting time. The setting is effective also during AT. If the setting is changed, control results change; redo the AT.
4.16 PV filter setting 4.16.1 PV filter setting This setting is a function to achieve the CR filter effect on the software by performing a primary delay calculation on the PV of the input 1. The filter effect is set with the damping time constant [t]. (Damping time constant is defined as time when PV reaches about 63% in a stepwise change of input.
4.17 Event alarm By setting the events 1 to 4 function setting, outputs of EV 1 to 4 are turned on if PV is located within the alarm range. Corresponding EV1 to EV4 lamps light up. By switching over the events 1 to 4 polarities, selection of open/closed is possible at the turn-on. Output is also turned on at occurrence of a loop abnormality when the events 1 to 4 function 2 setting is effective. * For loop abnormality, see Section 8.17 “ Loop abnormality.
4.20 Electric Power Outage Function Upon recovery of the electric power after its outage during a run, the status at the time of the outage is restored under the following conditions. Note that, if the PV at restoration is out of the range of [PV electric power outage restoration temperature width], the restoration is made as a stop. Alarm statuses of the event function are also restored. 1) If the step 1 is in the status of a timer run (SV=SLL): Restored at the location at the time of the outage.
5. Flow of Mode Change Operation and Run Operation 5.1 Primary Power Source in the OFF status Primary power source ON It takes about 2 seconds from the primary power source ON until the initial mode. Primary power source OFF 5.2 Initial mode 4 seconds elapsed In a stop: Display switchover key only In a run: Display switchover key: 3 seconds 5.4 Pattern No. setting mode Reset MODE key Reset MODE key: 3 seconds 5.3 Normal mode Reset MODE key +▽ key: 3 seconds Reset 5.5 Program setting mode 5.
Flow of the program setting mode Pattern No. setting mode Step 1 temperature setting Step 1 wait function existence/nonexistence setting MODE key DSP.CHG key + MODE key MODE key Step 1 time signal 1 function existence/ nonexistence setting Step 1 time signal 4 function existence/ nonexistence setting MODE key Step 1 operation amount limiter function setting MODE key * There are time signals 1 to 4.
Flow of the Common parameter setting mode Normal mode MODE key: 3 seconds ▽ key ▽ key MODE key To settings of SET1 MODE key To settings of SET2 △ key ▽ key ▽ key △ key MODE key ▽ key ▽ key ▽ key MODE key ▽ key ▽ key MODE key ▽ key ▽ key MODE key MODE key To settings of SET10 MODE key To settings of SET11 MODE key To settings of SET12 MODE key To settings of SET13 △ key To settings of SET7 ▽ key Flow of the Alarm temperature setting mode To settings of SET9 △ key To settings o
5.1 List of settings in the pattern No.
5.5 Common parameter setting mode SET 4 (1) SET04 1 SLH 2 SLL 3 CNT 4 DIR 5 MV1 6 TUN 7 ATG 8 ATC 9 AT1 10 AT2 11 AT3 12 ATALL 13 14 15 P1 I1 D1 16 PM1 17 P2 18 I2 19 D2 20 21 22 23 24 25 PM2 P3 I3 D3 T1 ARW 26 PS1 27 LOP1 28 CMOD 29 C1 30 CP1 Name Setting content Thermocouple/RTD input (SLL + 5.
5.5 Common parameter setting mode SET 4 (2) SET04 Name Setting content Initial value 31 MV2 Secondary control operating amount 0.0 to 100.0 (%) 32 Secondary control proportional band setting for PID PC1 No. 1 (low temperature) 0.10 to 10.00 (times) 1.00 33 PC2 Secondary control proportional band setting for PID No. 2 (intermediate temperature) 0.10 to 10.00 (times) 1.00 34 Secondary control proportional band setting for PID PC3 No. 3 (high temperature) 0.10 to 10.00 (times) 1.00 0.
5.
5.7 Common parameter setting mode SET 9 (2) SET09 Name Setting content Initial value With the selection of [MLF = 2,3], the following 18 to 41 are selectable.
5.8 Common parameter setting mode SET 10 SET10 1 INP1 2 FSH1 3 FSL1 4 PVG1 5 PVS1 6 7 PDF1 PDFS 8 DP1 5.
5.10 Common parameter setting mode SET 12 SET12 Name Setting content Initial value Press the MODE key for making a setting effective. 1 0 TOHO protocol PRT Communication protocol setting 1 MODBUS protocol (RTU mode) 0 2 MODBUS protocol (ASCII mode) ***1 1 bit ***2 2 bits **N* None **O* Odd No. 2 COM Communication parameter B8N2 **E* Even No.
5.12 List of the alarm temperature setting mode setting Name 1 E1H Event 1 upper limit setting 2 E1L Event 1 lower limit setting 3 E2H Event 2 upper limit setting 4 E2L Event 2 lower limit setting 5 E3H Event 3 upper limit setting 6 E3L Event 3 lower limit setting 7 E4H Event 4 upper limit setting 8 E4L Event 4 lower limit setting 5.13 Setting content Initial value See Section 6.6 “Common parameter setting mode SET 5 to 8.
7.
15 pcs RUN,OUT,EV1,EV2,EV3,EV4、TS1,TS2,TS3,TS4,TIME,AUTO,MAN U,AT,END Display/ LCD lamp green 2 pcs PTN,STP Accuracy of Thermocouples of K, J, T, E, R, S, B and N Setting Thermocouple Either larger ± (0.3 % + 1 digit) or ± 2 °C of the indicated value Indication /Set Note: ± 3 °C for -100 to 0 °C and ± 4 °C for -200 to -100 °C ting No specification for 400 °C or lower for B thermocouple * In standard environment conditions (23 ± 10 °C) Thermocouples of U and L: Either larger ± (0.
9.MAINTENANCE AND INSPECTIONS If any of the troubles still exists after following the above instruction, or for any other cases, contact our Sales Department. Troubles Check points Display does not come out.
TOHO ELECTRONICS INC. WEB.site http://www.toho-inc.com E-mail overseas@toho-inc.co.