User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 5-30
Set corresponding parameters into each bank.
Set the bank as the one to be used.
From ①
△/▽ key
Control setting mode
SET 04 screen
MODE key
Bank switchover
bANK * screen
bANK *: 0 to 7
Parameter setting
Other bank setting to be made
Bank already set
Control setting mode
SET 04 screen
Bank switchover
bANK * screen
MODE key
MODE key
Recording the switchover of banks
① Change of the control setting mode using “bank switchover” ---
The change is recorded when the MODE key is pressed (or when the screen moves to a next
screen.)
Take care that none is recorded when the △/▽ key is used for switchover.
② FUNC key .............. The change is recorded when the FUNC key is pressed.
③ DI ........................... The change is recorded when switchover is made in DI.
④ Communication ...... Only parameters for which limits are set when communication is used for
switchover. Recording is executed absolutely with “STR (store)” command.
STR .....See the chapter for communication in the operation manual.
Note Take care the switchover according to the items 2 to 4, since limiters may interfere with
setting values for parameters.
< Parameters with limits >
① Input type setting .................... INP 1, INP 2
② Decimal point position ........... dP 1, dP 2
③ Celsius/Fahrenheit .................. °C/°F
Example: Where the input type is changed from K thermocouple to T thermocouple
Setting values of SV limiter upper limit and lower limit change due to the setting range
narrower with T thermocouple.
<Measure> Set the parameter that interferes with the limits into the bank setting mode.