User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 5-35
■ Where the equipment is used as a simplified programmable controller (manual start and event * start)
Setting example where temperature is raised to 100 °C in 1 minute, maintained at 100 °C for 1 minute,
and then lowered to 0 °C in 1 minute
SEt03
KEY
Name
Setting content
Setting value
FU1
Function key 1 function setting
No setting of time for the key held
pressed/timer start/reset
04
SEt7/8
oUt3/4
Name
Setting content
Setting value
o3F
Target connection setting
Timer 1 output
5
o4F
Target connection setting
Timer 2 output
9
SEt14
tIME1
Name
Setting content
Setting value
tMF1
Function setting
Manual-start
2
oNt1
On delay timer
0 minute
00:00
oFt1
Off delay timer
1 minute
00:02
SEt15
tIME2
Name
Setting content
Setting value
tMF2
Function setting
Event 3 start
10
oNt2
On delay timer
2 minutes
00:02
oFt2
Off delay timer
1 minute
00:01
SEt20
bNK
Name
Setting content
Setting value
bnk01
Control setting
SV
bnk02
Ramp time setting
RMP
For the following setting, enter the inputs during the switchover in bANK (bank switching) in SET 4.
* Set bANK to “0.”
SEt04
CNt
Name
Setting content
Setting value
SV
Control setting
0 C
0
RMP
Ramp time setting
Setting turned off
0.0
* Set bANK to “1.”
SEt04
CNt
Name
Setting content
Setting value
SV
Control setting
100 C
100
RMP
Ramp time setting
To be raised by 100 °C in 1 minute
100.0
* Set bANK to “2.”
SEt04
CNt
Name
Setting content
Setting value
SV
Control setting
0 C
100
RMP
Ramp time setting
To be raised by 100 °C in 1 minute
100.0
* The bank cannot be switched over unless DI is set after the bank setting is complete.
SEt13
dI
Name
Setting content
Setting value
dIF
Function setting
Both DI 1 and DI 2 to be switched over
0011
Wire the equipment upon completion of setting.