48-7009-E 5-43
Star connection
Example: Where 3 heaters of 200 V and 2 kW are used
[When normal]
To equipment
CT input
To equipment
CT input
Load
Load
Load
Normal current is 5.8 A {10 A × (1/3)} for each phase.
[When disconnected in between phases]
To equipment
CT input
To equipment
CT input
Load
Load
Load
Disconnected
Current when disconnected in between phases = 10 A × (1/3) × (3/2) = 5A
[When disconnected on load side]
To equipment
CT input
To equipment
CT input
Load
Load
Load
Disconnected
Current when disconnection occurs on the load side = 10 A × (1/3) × (3/2) = 5A
The CT 1 abnormal current value setting value for this connection is 5.4 A {= (5.8 + 5)/2}.