User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 5-46
5.4.9 Concurrent temperature ascent function
■ What the concurrent temperature ascent is
• When a concurrent temperature ascent control is executed for multiple channels using the RS-485
communication function, a target value can be reached for each channel at the same clock time,
disregarding characteristics of each channel through assigning master or slave to the channels.
The channel that requires the longest time for reaching the target value from the start of the control
is assigned as a master and others as slaves.
• The concurrent temperature ascent function is activated when operation starts, including when
power turns on, or setting value is changed, and terminated when the master reaches the target value.
Controller 1 ch Controller 2 ch Controller 3 ch Controller 4 ch
Heater Heater Heater Heater
Sensor Sensor
Sensor
Sensor
Oven
Input Output Input Output Input Output Input Output
• How to use the function
1) Set the communication protocol setting (SEt 17) to TOHO protocol.
2) Set the communication switchover setting (SEt 17) to a concurrent temperature ascent master
for a channel that requires the longest time to reach the target value, and to concurrent
temperature ascent slaves for others.
3) Set the primary control sensitivity setting (SEt 04).
Set the sensitivity to such a degree that no chattering is generated, as the slave sides are
ON/OFF-controlled to the present temperature on the master during concurrent temperature
ascent.
Note Precautions on the use
1) Conduct the auto-tuning for each channel as needed.
2) Do not execute external communication during the use of the concurrent temperature ascent function.