User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 5-50
*1: Operating type setting (C/P)
Set “operating method.”
Setting range Initial value: 0 in constant value run mode
0: Constant value run mode (program run mode OFF)
1: Program run mode (program run mode ON)
*2: Program rum mode setting (PGMd)
Set “return operating method” and “operation method after program run” in case of power failure
during a program run.
Setting range Initial value: 0 Program 1 (without power failure compensation)
0: Program 1 (without power failure compensation)
1: Program 2 (without power failure compensation)
2: Program 1 (with power failure compensation)
3: Program 2 (with power failure compensation)
• Program 1: Control stops when a program run ends. When a run ends, ENd is displayed and
control stops.
• Program 2: Control remains active at a status of the last step even after a program run ends.
Control continues even though ENd is displayed after a run ends. Control becomes in a stop
status by manual operation (key operation) or DI entry.
Note The SET 4 control mode setting (Md) becomes inactive in program rum mode (C/P 1). Only
constant value rum mode is active.
Regarding power failure compensation
Upon return from a power failure with “With power failure compensation,” the run restarts from
the step being in progress at the time of the power failure.
“Current step,” “repetitive count” and “remaining time” are stored.
In case of power failure, the status returns to that last-stored in the step, and the run restarts
provided that the setting condition of the power failure compensation range setting (PoC) is met.
Note Note that time error is generated within a step even though a run restarts from the middle of a
program run if the return condition (power failure compensation range setting) is met.
Note The return conditions is that the difference of the PV values between at return and before return is
smaller than the power failure compensation range setting (PoC) as shown in the formula below:
Condition Power failure compensation range setting (PoC) (PV value at return) (PV value
before return)
*3: Power failure compensation range setting (PoC)
Set the criteria range for the condition described above for return from a power failure.
Setting range Initial value: 0
Temperature input (C): 0 to 999 (0.0 to 999.9) Always return at 0.
Analog input (digit): 0 to 9999 Always return at 0.
Note Upon return from a power failure, no return operation is performed in case of disconnected or
failed sensor regardless the (PoC) setting value. The run status is of program run in stoppage.