User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 5-72
*1: Bank automatic switching function selection (bAF)
Set the bank automatic switching ON/OFF.
Setting range Initial value: 0 Bank automatic switching run OFF
0: Bank automatic switching run OFF
1: Bank automatic switching run ON
*2: Bank automatic switching source setting (bAS)
Select an input source. The bank is switched in accordance with the input of the source selected.
Setting range Initial value: 0 Select a SV value
0: Select a SV value {only local and remote (only option Y)}.
1: Select a ramp SV value
2: Select a PV value
Note When [bAF 1], the [SET 04 SV] value is selected for AT (auto tuning) regardless of the source
setting, which is used for bank auto switching.
If the zone threshold* setting (PM*) is set, a bank matching the SV value is selected based on the
result from AT (auto tuning). That is, a result from AT is reflected to the bank selected with a
threshold. As such, if a [P, I, d] value is desired to set for each temperature, perform AT (auto
tuning) after setting said value in the bank.
*3: Zone threshold* setting [PM 1 to PM 7]
A threshold is set for automatically switching a bank. Seven threshold values at most can be set
for eight banks.
Setting range: SLL to SLH Initial value: SLH
*4: Zone threshold switching sensitivity range setting (ASC)
A sensitivity range set in ASC is provided for each threshold [PM*] used for bank automatic
switching. (See the diagram below.) The sensitivity range is common to each threshold.
Setting range: During the temperature input 0 to 999 (0.0 to 999.9) (C) Initial value: 0
During analog input 0 to 9999 (digit)
Auto-Switching
Source
BANK0
BANK1
BANK2
BANK3
BANK4
BANK5
BANK6
BANK7
PM1
PM2
PM3
PM4
PM5
PM6
PM7
SLH
SLL
PM*
(*=1~7)
Magnified
Drawing
ASC
When
"increasing"
Auto-Switching
Source
When
"decreasing"
Outset of
BANK
switching
Outset of
BANK
switching
Auto-Switching
Source
The sensitivity range is effective if a remote SV or PV is selected for the bank automatic switching
source setting [bAS]. Other than this, the range is ineffective.
Note Condition on enabled ASC setting
When [bAS 2]
When SET 02 [LR 1, 2] with [bAS 0]
Note Condition on unable ASC setting
When [bAS 1]
When SET 02 [LR 0], even though [bAS 0]
PM*
(*=1-7)