PV compensation gain/PV compensation zero setting
SETTING CONTENTS
INITIAL
VALUE
4
PV CORRECTION FUNCTION SETTING 3
0:PV Gain / Zero Point Correction
1:PV XY 2-Point Correction
0
5
PVCorrection Gain Setting
0.500~2.000(X)
1.000
6
PV Correction Zero Setting
Thermocouple
-999.9~999.9()
-999~999()
0
Voltage-Current Input
-9999~9999(digit)
7
PX1
PV Before Correction Lower Limit Value Setting 3
Setting RangeSetting Range Lower Limit to (PX 2 -
1) or Setting Range Lower Limit to
(PX 2 1.0)
Setting Range Lower Limit to (PX 2-
10-digits)
Setting Units1 or 0.1, 1-digit
0
8
PX2
PV Before Correction Upper Limit Value Setting 3
Setting Range(PX 1 + 1) to Setting Range Upper
Limit , or (PX 1 + 1.0) to Setting
Range Upper Limit
(PX 1 + 10-digits) to Setting Range
Upper Limit
Setting Units1 or 0.1, 1-digit
1200
9
PY1
PV After Correction Lower Limit Value Setting 3
Setting RangeSetting Range Lower Limit to (PY 2 -
1) or Setting Range Lower Limit
(PY 2 1.0)
Setting Range Lower Limit to (PY 2 -
10-digits)
Setting Units1 or 0.1, 1-digit
0
10
PY2
PV After Correction Upper Limit Value Setting 3
Setting Range(PY 1 + 1) to Setting Range Upper
Limit , or (PY 1 + 1.0) to Setting
Range Upper Limit
(PY 1 + 10-digits) to Setting Range
Upper Limit
Setting Units1 or 0.1, 1-digit
1200
When the PV Correction Function Setting (PVF1=0), PX1, PX2, PY1, PY2 are not indicated.
When PV Correction Function Setting (PVF1=1), PVG1, PVS1 are not indicated.
PV compensation gain setting: PV (measurement value) for the input 1 is multiplied by the compensation value.
Setting example: Where PV of the equipment is displayed for 90°C and the actual temperature is 100°C, and the display is
to be compensated to 100°C, using the PV compensation gain setting.
The display after PV compensation is about 100°C = 90°C (before PV compensation) × 1.111.
PV
PVG 1 = 100/90 = 1.111 times
100
90
100
After PV compensation
Before PV compensation
Actual temperature