User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 6-6
PV X-Y 2-POINT CORRECTION SETTING
Determine any two points within the input range (upper and lower limit), then convert to corrected value to the PUV of Input 1.
For Example)
When the PV of the product is;
90℃ indication but actual temp. is 100℃
310℃ indication but the actual temp. is 300℃
If these are to be corrected by 2-point Correction Setting;
PV before correction: PX 1 = 90℃, PX 2 = 310℃
PV after correction: PY 1 = 100℃, PX 2 = 300℃
PX 1 PV Before Correction Lower Limit Value Setting
Setting Range:Setting Range Lower Limit to (PX 2 - 1℃) or Setting Range Lower Limit to (PX 2 –1.0℃)
:Setting Range Lower Limit to (PX 2 – 10-digits)
Setting Units:1℃ or 0.1℃, 1-digit
PX 2 PV Before Correction Upper Limit Value Setting
Setting Range:(PX 1 + 1℃) to Setting Range Upper Limit , or (PX 1 + 1.0℃) to Setting Range Upper Limit
:(PX 1 + 10-digits) to Setting Range Upper Limit
Setting Units:1℃ or 0.1℃, 1-digit
PY 1 PV After Correction Lower Limit Value Setting
Setting Range:Setting Range Lower Limit to (PY 2 - 1℃) or Setting Range Lower Limit to (PY 2 –1.0℃)
:Setting Range Lower Limit to (PY 2 – 10-digits)
Setting Units:1℃ or 0.1℃, 1-digit
PY 2 PV After Correction Upper Limit Value Setting
Setting Range:(PY 1 + 1℃) to Setting Range Upper Limit , or (PY 1 + 1.0℃) to Setting Range Upper Limit
:(PY 1 + 10-digits) to Setting Range Upper Limit
Setting Units:1℃ or 0.1℃, 1-digit
NOTE: - As much as possible, set the difference in the value of Before Correction and After
Correction bigger within the realizable range. When the difference is small, the margin of
error might be bigger.
- When the slope of PX 1 and PX 2 (before correction) is set to 1 and when the slope after
Correction becomes less than 1, the indication range in each input type becomes narrow.
PX1
PY1
PY2
PX2
After Correction
Before Correction
PV値
Actial Input
Upper Limit Value
Lower Limit Value