User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 6-8
6.2 Remote SV input type setting
■ Remote SV input type setting
SEt02
INP2
Setting content
Initial value
1
INP2
Press the MODE key for making a setting effective (including reverse feed).
18
16 to 20
See the remote SV input type setting table.
Set the input type of the remote SV input.
The remote SV input is a multiinput of voltage and current. Set the remote SV input according to the input being used.
■ Remote SV input type setting table
Setting
No.
Input type
Connection
Measurement/
setting range
Indicator resolution
Accuracy
16
0 - 1 VDC
I/V
-19999 to +29999
Display resolution to be
20000 or less
Random change of
decimal point
position allowed
± 0.3 % ± 1 digit of full scale
17
0 - 5 VDC
I/V
18
1 - 5 VDC
I/V
19
0 - 10 VDC
I/V
20
4 - 20 mADC
I/V
*1 The display range of analog input is min. - 19999 digits and max. +29999 digits. The range, however, can be narrowed by
setting the scaling upper limit (FSH 2) and lower limit (FSL 2) settings. See below for the narrowed display range.
<Where input is 0 - 1 V/0 - 5 V/0 - 10V>
• Display of the lower limit side: Up to - 2 % of the full scale
• Display of the upper limit side: Up to + 12 % of the full scale
<Where input is 1 - 5 V/4 - 20 mA>
• Display of the lower limit side: Up to - 12 % of the full scale
• Display of the upper limit side: Up to + 12 % of the full scale
Full scale is defined as the range from FSL 2 to FSH 2.
Remote SV input connection table
Model
TTM-200 Series
Model No.
204
205
209
207
Connection
Wiring
Terminal No.
Terminal No.
Terminal No.
I/V
17
18
11
12
■ Display scaling upper limit/lower limit setting
SEt02
INP2
Setting content
Initial value
2
FSH2
FSL 2 to SV setting range upper limit
The unit depends on the input type setting for the input 1.
1200
3
FSL2
SV setting range lower limit to FSH 2
The unit depends on the input type setting for the input 1.
0
Set the display scaling upper limit/lower limit for the remote SV input.
The input type of the remote SV input can be set only for voltage or current input.