User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 6-10
PV compensation zero setting: PV (measurement value) for the remote SV input is added by the compensation value.
Setting example: Where PV of the equipment is displayed for 90°C and the actual temperature is 100°C, and the display is
to be compensated to 100°C, using the PV compensation zero setting.
The display after PV compensation is 100°C = 90°C (before PV compensation) + 10°C.
PV
100
90
10
0
100
PVS 2=10℃
After PV compensation
Before PV compensation
Actual temperature
* See below for an equation for combination of the PV compensation gain setting and PV compensation zero setting.
PV of remote SV input = before PV compensation × PV compensation gain setting + PV compensation zero setting
Note
(1) Take care that stability of the measurement value may deteriorate when the PV compensation gain setting is large.
(2) Take care that the display range may change when the PV compensation gain setting is set to a multiplication factor of 1
or smaller.
Setting example: Where K thermocouple input for - 200.0 to 1372.0°C
PV compensation gain setting: Multiplied by 0.5 - 100.0 to 686.0°C
PV compensation gain setting: Multiplied by 0.1 - 20.0 to 137.2°C
(3) Take care that the display range may change when the PV compensation zero setting is set to a value other than 0.
Setting example: Where K thermocouple input for - 200 to 1372°C
PV compensation zero setting: + 100°C - 100 to 1372°C
PV compensation zero setting: - 100°C - 200 to 1272°C
* The display range for analog input is not affected by the PV compensation zero setting.