User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 6-13
(6) ENT
The FUNC key is used as a setting recording key.
Take care that a move to the next parameter without recording results in a return of the setting to the one before the change.
Note For moving to another function from the ENT function, select the desired function and press the FUNC (ENT) key.
(7) Bank switchover
The FUNC key is used as a key for switching over the banks 0 to 7.
(8) Control mode/manual
Pressing the FUNC key results in the switchover from the control mode to the manual or vice versa.
(9) SV/MV SWITCH-OVER By pressing the FUNC-Key, The indication at the SV indication window can be
changed to SV or MV.
(10) CONSTANT OPERATION MODE/PROGRAM OPERATION MODE SWITCH-OVER
By pressing the FUNC-key, mode can be switched to operation mode.
Switching between the Constant Operation Mode and the Program Mode can be done.
(11) STEP FORWARD
By pressing the FUNC-key, the steps can be forwarded during the program operation;
NOTE: This function is effective only when the Program Operation is being selected.
NOTE: When the bank no. at the auxiliary indication is not being shown, nothing happens
even if the step forward key is pressed.
(12) PAUSE
By pressing the FUNC-key, the Program Operation can be stopped temporarily.
Switching between Pause – In Operation will be made.
NOTE: This function is effective only when the Program Mode is being selected.
(13) By pressing the FUNC-key, direct jump to SET 22 Parameter Setting Mode can be made.
To go back to the operation mode from SET 22, press MODE key for 2 seconds, or press the FUNC-key.
NOTE: This function is effective only when the Program Mode is being selected.
■Key Lock Setting
SEt03
KEY
Setting Contents
Initial
Value
6
LoC
0
Lock OFF
0
1
All Lock
2
Operation Mode Lock
3
Lock except Operation Mode
4
All Lock (during RUN only) 3
5
Operation Mode Lock (during RUN only) 3
6
Lock except operation mode lock(during
RUN only) 3
7
Parameter Mode Lock (during RUN only) 3
Set the lock for keys.
Locked parameter settings cannot be changed using the / key.
LoC=4-7 limits the lock depending on the control condition.
The key-lock setting is effective only in (MD=RUN) during the constant operation, and in
(in-operation or pause) during the program operation.
LoC=7 locks the parameter setting mode shift depending on the control condition.
Changing to Parameter Setting Mode cannot be made in (MD=RUN) during the constant
operation, and in (in-operation or pause) during the program operation.
NOTE: Conditions in LoC=7 Key-Lock
It is necessary that either more than 1 Di is set at DIF=2, or more than 1 key function is FU=2.