User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 6-14
6.4 Control function setting
■ Bank switchover/Bank Upper Limit Setting
SEt04
CNt
Setting content
Initial value
1
bANK
0 to 7
Bank 0 to 7
0
bANKH
Bank Upper Limit Setting 0 to 7 3
7
Switching over to the banks 0 to 7 is executed.
Switchover to either one of the banks 0 to 7 results in that a parameter set in the memory bank is switched over to a setting
value for each bank.
Note The setting is determined by pressing the MODE key or FUNC key (only for setting the screen reverse feed).
For the Bank Function, please refer to Operation Manual Bank Function (P5 – 28 up to 30).
■ Control setting
SEt04
CNt
Setting content
Initial value
3
SV
SLL to SLH
0
Set a target value (SV) for a control.
Allowable setting range is from SLL (SV limiter lower limit) to SLH (SV limiter upper limit).
■ SV limiter upper limit/lower limit
SEt04
CNt
Setting content
Initial value
4
SLH
Thermocouple/resistance temperature detector input
(SLL + 5.0) to SV setting range upper limit (°C)
(SLL + 5) to SV setting range upper limit (°C)
1200
Voltage/current input
(SLL + 50) to SV setting range upper limit (digit)
12000
5
SLL
Thermocouple/resistance temperature detector input
SV setting range lower limit to (SLH - 5.0) (°C)
SV setting range lower limit to (SLH - 5) (°C)
0
Voltage/current input
SV setting range lower limit to (SLH - 50) (digit)
Set the SV upper limit/lower limit.
• SV limiter upper setting range
For input of thermocouple/resistance temperature detector
: (SLL + 5) to Input 1 setting range upper limit [°C] (Decimal point position setting 0)
: (SLL + 5.0) to Input 1 setting range upper limit [°C] (Decimal point position setting 0.0)
For input of voltage/current
: (SLL + 50) to Input 1 setting range upper limit [digit]
• SV limiter lower setting range
For input of thermocouple/resistance temperature detector
: Input 1 setting range lower limit to (SLL - 5) [°C] (Decimal point position setting 0)
: Input 1 setting range lower limit to (SLL - 5.0) [°C] (Decimal point position setting 0.0)
For input of voltage/current
: Input 1 setting range lower limit to (SLL - 50) [digit]
For input 1 setting range upper limit/lower limit, see the input 1 type setting table on page 6-2.