User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 6-15
■ Control mode
SEt04
CNt
Setting content
Initial value
6
Md
RUN
Control start
RUN
MAN
Manual
RdY
Control stop
tIME1
Timer 1 operation
tIME2
Timer 2 operation
tIME3
Timer 3 operation
Set the control mode.
Control stop (RdY): Primary/secondary operating amount limiter lower limit is output.
Control start (RUN): Normal control is executed.
Manual (MAN): Operating amount set in the primary/secondary operating amount is output.
Timer interlocking control (tIME 1 to 3): A control where the normal control and timer operation are interlocked is executed.
For start (RUN)/stop (RdY)/manual (MAN) of control, see section “5.4.3 Mode/manual function” on page 5-28.
For timer interlocking control (tIME 1 to 3), see section “5.4.5 Timer function” on pages 5-32 to 37.
■ Control type setting
SEt04
CNt
Setting content
Initial value
7
CNt
0
Primary --- None
Secondary --- None
1
1
Primary --- PID control
Secondary --- None
2
Primary --- ONOFF control
Secondary --- None
3
Primary --- PID control
Secondary --- PID control
4
Primary --- PID control
Secondary --- ONOFF control
5
Primary --- ONOFF control
Secondary --- ONOFF control
6
Primary --- position proportional
Secondary --- position proportional
Set the control type (method).
Control types of primary and secondary control outputs that are set on this equipment can be assigned to the methods of 0 to 6.
For the content of the assignment, see the setting content listed above.
Note
(1) In case that the control type is set to 3 (primary/secondary PID control) and the tuning type to 3, 4 or 5, take care that the tuning
type changes to 1 (primary tuning) in conjunction with the change of the control type.
(2) Take care that the position proportional control (CNt: 6) is selectable even when the primary/secondary control output is not set
for the target connection setting.
■ PID control type/type B mode
SEt04
CNt
Setting content
Initial value
8
tYP
0
type A (normal PID control)
1
1
type B (overshoot suppression function)
2
type C (disturbance suppression function)
9
bMd
0
Overshoot suppression --- moderate
1
1
Overshoot suppression --- intermediate
2
Overshoot suppression --- intense
Set the PID control type.
For the use of the equipment in setting of the control type to be the PID control, a selection can be made among three control types of
0 (type A) to 2 (type C), whichever is best suited for the application.
Note The type B mode can be set when the PID control type is set to 1 (type B). In the type B mode, a result from integration (I) or
differentiation (d) of the auto-tuning is multiplied by a coefficient. The intermediate type is same value as it is. The type C
(disturbance suppression function) cannot be set when the self-tuning is set in the tuning type setting.
For control characteristics of each control type, see section “5.4.1 Auto-tuning (AT) function” on pages 5-23 to 25.