User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 6-17
■ Primary control operating amount
SEt04
CNt
Setting content
Initial value
11
MV1
MLL 1 to MLH 1 (%)
0.0
The screen is for displaying the operating amount for the primary control.
The operating amount cannot be set for the normal control.
The operating amount can be set only when the control mode is set to manual.
■ Primary control output gain setting
SEt04
CNt
Setting content
Initial value
12
MV1G
0.0 to 1000.0 (%)
100.0
The operating amount (MV 1) for the primary control is multiplied by a compensation value.
[Operating amount for the primary control] = [Operating amount for the primary control before compensation] × [Primary
control output gain setting]
Note A change of the output gain setting may result in no provision of best suited PID parameter in AT.
Note Each limiter is output with a high priority, when the following is set: the primary control operating amount limiter upper limit
setting or primary control operating amount limiter lower limit setting.
Change of the output amount when the output gain setting is set to 70.0 %
100.0%
70.0%
50.0%
35.0%
Output operating
amount calculated
Operating amount
Output operating amount
that is actually output
SV temperature reached
Measurement temperature
Setting example:
When control characteristics in 100 VAC is desired to be maintained also in 120 VAC;
100 VAC and 100 W 120 VAC and 144 W, assuming that the heater resistance of 100 is identical for both 100 VAC and
120 VAC
100 W ÷ 144 W = 69.4 %
Thus, by setting the output gain setting to 69.4 %, control characteristics in 120 VAC can be expected to be analogous to those
in 100 VAC.
NOTE: In case the loop disconnection is used when the output gain setting is at 50.0%, make the working volume limiter the same as
that of output gain.