User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 6-19
■ AT start screen
SEt04
CNt
Setting content
Initial value
16
At
Use the / key for start and stop.
PV/SV is displayed during AT.
oFF
The screen is used for starting AT.
Pressing the key or key allows start/stop of AT.
After setting the AT start/stop in the key function setting, pressing the FUNC key allows the AT start/stop. See page 6-11.
After setting the AT start/stop in the DI function setting, DI allows the AT start/stop. See pages 6-57 and 58.
Note The AT start/stop is not allowed on the AT start screen when the AT start/stop is set for DI or the FUNC key.
■ Proportional band setting
SEt04
CNt
Setting content
Initial value
17
P1
0.1 to 200.0 (%)
3.0
Set the proportional band.
The proportional band for the heating cooling control is the one on the heating side.
The proportional band for the heating control is located as shown in the diagram below.
The proportional band for the cooling control is located in the upper side of SV in the diagram.
Temperature
Time
Proportional
band range
SV
The proportional band range can be calculated, using the equation below.
Proportional band range = (SLH - SLL) × P 1
SLH: SV limiter upper limit
SLL: SV limiter lower limit
Example: When SLH = 1200°C, SLL = 0°C, and P 1 = 3.0 %;
(1200°C - 0°C) × 3 % = 36°C.
Thus, the output gradually decreases from the one at the temperature 36°C below SV.
In general, wider proportional range results in a slower initial rise.
A narrower proportional range may result in that the control goes too far (overshoot), or forms waves (hunting) to cause
unstable output, although the initial rise is faster.