User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 6-20
■ Integral time setting
SEt04
CNt
Setting content
Initial value
18
I
0 to 3600 (seconds)
0
Set the integral time.
Setting of 0 second results in no integral operation.
Both heating and cooling sides share to use this setting in the heating cooling control. (Individual setting is not allowed.)
The integral operation is an operation that makes the deviation between the setting value and measurement value, which is
generated in the proportional control, approach 0.
Temperature
Time
Deviation
Setting value
(SV)
The integral time is a value, in the unit of second, that defines intensity of the integral operation.
A smaller time value setting is equivalent to a more intense operation. (Because the value deviated is attempted to return in
the set time.)
■ Derivative time setting
SEt04
CNt
Setting content
Initial value
19
d
0 to 3600 (seconds)
0
Set the derivative time.
Setting of 0 second results in no derivative operation.
Both heating and cooling sides share to use this setting in the heating cooling control.
The derivative operation is an operation that works to return fast to the original control state by supplying a large operating
amount against drastic disturbances.
The output provided by the derivative operation is proportional to the time derivative value of the measurement value.
The proportional and integral operations are corrective operations, so their responses tend to be slow to drastic temperature
changes (or disturbances). The derivative operation supplements such a shortcoming.
The derivative time is a value, in the unit of second, that defines intensity of the derivative operation.
A larger time value setting is equivalent to a more intense operation. (Because the interval to pick a variance becomes larger.)