User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 6-34
■ Secondary control operating amount
SEt04
CNt
Setting content
Initial value
38
MV2
MLL 2 to MLH 2 (%)
0.0
The screen is for displaying the operating amount for the secndary control.
The operating amount cannot be set for the normal control.
The operating amount can be set only when the control mode is set to manual.
■ Secondary control output gain setting
SEt04
CNt
Setting content
Initial value
39
MV2G
0.0 to 1000.0 (%)
100.0
The operating amount (MV 1) for the secondary control is multiplied by a compensation value.
[Operating amount for the secondary control] = [Operating amount for the secondary control before compensation] ×
[Secondary control output gain setting]
■ Secondary control proportional band setting
SEt04
CNt
Setting content
Initial value
40
P2
0.10 to 10.00 (times)
1.00
Set the secondary control proportional band.
The proportional band of the secondary control is set in a multiplication factor of 0.1 to 10 with respect to the proportional
band of the primary control.
The proportional band of the secondary control is always set in opposite side to the proportional band of the primary control
about SV.
Setting example: Where the proportional band range P2 of the secondary control is set to 2.00, P2 is twice as large as the
proportional band range P1 of the primary control.
Primary control proportional band
Temperature
SV
Secondary control
proportional band
When P2 = 2.00 is set, the proportional
band range of the secondary control is
twice as large as that of the primary
control.