User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 6-41
■ Secondary control loop anomaly PV change threshold
SEt04
CNt
Setting content
Initial value
49
PS2
Thermocouple/resistance temperature detector input
0.0 to 999.9 (°C)0 to 999 (°C)
Applicable only for time judgment when PS 2 = 0 (LoP2)
0
Voltage/current input
0 to 9999 (digit)
Applicable only for time judgment when PS 2 = 0 (LoP2)
Set the secondary control loop anomaly PV change threshold.
The function is to detect an abnormality in the control loop.
When the time satisfying threshold of TS2 or MS2 exceeds LOP2, the loop abnormality is determined as
detected.
For details, see section “Loop abnormality function” on pages 5-38 and 39.
- The control loop anomaly PV change threshold is judged at each “LoP2” time.
A loop abnormality is determined if each change threshold is judged to be equal to or below “PS2.”
- When [PS2 = 0] is true, only time judgment is executed using LOP2.
When the time satisfying threshold of TS2 or MS2 exceeds LOP2, the loop abnormality is determined as detected.
SV
PV
(PS2)
(LoP2)