User Manual

Table Of Contents
48-7009-E 6-42
Secondary control loop abnormality time setting
SEt04
CNt
Setting content
Initial value
50
LoP2
0 to 9999 (seconds)
0
Set the secondary control loop abnormality time setting.
The function is to detect an abnormality in the control loop.
- The control loop anomaly PV change threshold is judged at each LoP2 time.
A loop abnormality is determined if each change threshold is judged to be equal to or below PS2.
For details, see sectionLoop abnormality function on pages 5-38 and 39.