User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 6-47
■ Valve motor stroke time
SEt04
CNt
Setting content
Initial value
58
VLt
0.1 to 999.9 (seconds)
3.0
Set the valve motor stroke time.
Output is generated for the time set for VLt (valve motor stroke time) when PV (measurement value) changes in range by the
amount identical to the proportional band range.
For the valve motor stroke time, set the time period from full open to full close of the valve used.
Setting example: For the position proportional control of the heating control, where settings are as follows: SV of 200°C,
proportional band range of 200°C and VLt of 10 seconds.
Output change is described as an example when the temperature changes as shown in the diagram below.
The temperature changes from 0 to 200°C, where the amount of the change is equivalent to the
proportional band range. This change results in the secondary control output (close) being output for 10
seconds, which is equivalent to the setting time for VLt.
Then, the temperature changes from 200°C to 100°C, which is equivalent to the half the proportional band
range. This change results in the primary control output (open) being output for 5 seconds, which is
equivalent to a half the setting time for VLt.
100℃
Temperature
200℃
0℃
SV=200℃
Proportional
band range
200℃
Secondary control
output (close)
Primary control
output (open)
10 seconds
5 seconds
Note Take care when selecting a valve, as the output is not turned off when the operating amount is in either 0 % or 100 %.