User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 6-51
■ Event function 1 operation
The operation range (range for turn-on) of the event function 1 assigned for outputs 1 to 7 is set in terms of the event function 1
setting, and event upper limit, event lower limit and event sensitivity settings. See below for the event function 1 operation
range.
■ Event function 1 operation range table
1 Deviation upper and lower limits
5 Absolute value upper and lower limits
E*C
SV
E*C
E*L E*H
△
0℃
E*C E*C
E*L
E*H
2 Deviation upper limit
6 Absolute value upper limit
SV
E*C
E*H
△
0℃
E*C
E*H
3 Deviation lower limit
7 Absolute value lower limit
E*C
SV
E*L
△
0℃
E*C
E*L
4 Deviation range
8 Absolute value range
E*C
SV
E*L E*H
△
E*C
E*C
E*C
0℃ E*L
E*H
: Event function 1 operation range,
: Location of SV, E * C: Event sensitivity
E * H: Event upper limit setting (The chart in the table is for plus setting; for minus setting, the chart is to be reversed about SV or 0°C.)
E * L: Event lower limit setting (The chart in the table is for plus setting; for minus setting, the chart is to be reversed about SV or 0°C.)
Note Setting “none” for the event function 1 results in no operation. (For the symbol “*,” a numerical character from 1 to 7 for actual output is to be put
in.)
Explanation on the event function 1 add-on function/control mode interlocking function
Hold: A function that holds and continuously provides the event output after it is once provided, even when PV is out of the operation range of the
event function 1
Note The event output held is released when the power returns or the event upper/lower limit setting changes.
In addition, the hold is released due to a SV change when the event range is set in terms of deviation.
Standby: A setting where no output is initially provided but the product stands by even when PV is within the operation range of the event function 1, at
power-on or setting change. The event output is provided when PV is out of the operation range once and returns within it.
This function is an effective function for the product not to operate in case of PV going in the operation range at power-on or setting change.
Delay: A delay time is set where the time from PV being in the operation range of the event function 1 to event-outputting is to be delayed.
This function is an effective function for the product not to event-output for a predetermined time after PV being in the operation range.
Note No delay time is effective when PV moves from within the operation range of the event function 1 to out of the operation range.
Interlocking function: A control mode is set to operate the event function 1, using the control mode interlocking function.
A combination with standby-sequence is described in the next page.