User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 6-52
1) State when no event has occurred
No event occurs when RUN/READY is switched over.
2) Standby state
No event occurs when RUN/READY is switched over.
3) State when an event has occurred (an event occurs when the event moves out from the standby state.)
By switching over from RUN to READY, the event turns to OFF. It goes to 2)standby state.
■ Event function 2 setting (PV abnormality)
SEt05
oUt1
to
SEt11
oUt7
Setting content
Initial value
7
E1F2
to
E7F2
Function
000
**0
Nonexistent
**1
Existent
Add-on function
*0*
None
*1*
Hold
*2*
Delay
*3*
Hold + delay
Control mode interlocking function
0**
All modes
1**
RUN/MAN mode only
2**
RUN mode only
Set the event function 2 (PV abnormality).
Event function 2 is a function to output signals (ON/OFF) from the outputs 1 to 7 that are assigned for the event function 2
when an abnormality is generated in the input 1.
This function is effective when the event function 2 is set to **1.
This function is useful in case of improper setting of the input 1 type, alarming for input improper wiring, disconnection or
short, or start/stop of other systems.
This function can be used when the target connection for the outputs 1 to 7 are set for the event output.
Note Take care that the event function 2 may event-output when input 1 type is being changed.
For the operation range of the event function 1 and each setting value, see section of event function 1 operation on page 6-49.
For the add-on function of the event function 2 and the control mode interlocking setting, see again section of event function 1
operation on page 6-49
Example of PV abnormal setting: In the case of PV Abnormal, No Added Function, Control Mode
Interlock Full Mode, set to “001”.