User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 6-59
6.7 DI setting
■ DI function setting
SEt13
dI
Setting content
Initial value
1
dIF
Press the MODE key for making a setting effective (including reverse feed).
0000
****
||||
|||+-- DI 1 setting (settable when an option existent)
||+--- DI 2 setting (settable when an option existent)
|+---- DI 3 setting (settable when an option existent)
+----- DI 4 setting (settable when an option existent)
Active
0
None
None
1
Bank switchover
Bank switchover
2
When Constant operation
Mode
MD
When Program Mode
Start
When Constant operation
Mode
READY
When Program Mode
stop
3
MD
MANUAL
4
Reverse operation
Forward operation
5
AT stop
AT start
6
Timer stop
Timer start
7
Constant Operation Mode
Program Mode 3
8
-
Step Forward 3
(during program mode)
9
-
Pause 3
(during program mode)
A
nerlock
- 3
Set the DI function.
0: No DI function
1: Bank switchover is executed.
Bank selection table per DI 1 state
DI1
DI3
DI2
DI1
0
Bank 0
0
0
0
Bank 0
1
Bank 1
0
0
1
Bank 1
0
1
0
Bank 2
DI2
DI1
0
1
1
Bank 3
0
0
Bank 0
1
0
0
Bank 4
0
1
Bank 1
1
0
1
Bank 5
1
0
Bank 2
1
1
0
Bank 6
0: Inactive
1: Active
1
1
Bank 3
1
1
1
Bank 7
The parameters change right after switchover when the bank is changed per DI.
2: <During Constant Operation Mode> Switching of Control Mode and STOP.
<During the Program Mode> Switching of In-Operation and Operation Stop.
3: Switching of AUTO & MANUAL is done
4: Switching of Output Movement (forward / reverse movement) is done.
5: The Star & Stop of Auto-Tuning of PID Control is done.
Maintain the DI to active condition until the auto-tuning is completed.
In case the operation is suspended half-way, the auto-tuning will stop.