User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 6-65
6.9 Communication function setting
■ Communication protocol setting
SEt17
CoM
Setting content
Initial value
1
PRt
Press the MODE key for making a setting effective (including reverse feed).
0
0
TOHO protocol
1
MODBUS protocol (RTU mode)
2
MODBUS protocol (ASCII mode)
Set the communication protocol (communication procedure).
For details of communication, see “TTM-200 series operation manual - communications.”
■ Communication parameter setting
SEt17
CoM
Setting content
Initial value
2
CoM
***1
Stop bit length 1 bit
b8N2
***2
Stop bit length 2 bits
**N*
Parity none
**o*
Parity odd No.
**E*
Parity even No.
*7**
Data length 7 bits
*8**
Data length 8 bits
N***
BCC check nonexistent (settable for TOHO protocol)
b***
BCC check existent (settable for TOHO protocol)
For MODBUS (RTU)
Settable only with 8N2, 8N2, 8o1, 8o2, 8E1 and 8E2.
For MODBUS (ASCII)
Settable only with 7N1,7N2,7o1,7o2,7E1,7E2,
8N1,8N2,8o1,8o2,8E1,8E2
The following is set for communication data: stop bit length, parity and BCC check existent/nonexistent.
For details of communication, see “TTM-200 series operation manual - communications.”
■ Communication speed setting
SEt17
CoM
Setting content
Initial value
3
bPS
2.4
2400 bps
9.6
4.8
4800 bps
9.6
9600 bps
19.2
19200 bps
38.4
38400 bps
Set the communication speed.
The term bps (bits per second) refers to the number of bits allowed in communication in a second.
For details of communication, see “TTM-200 series operation manual - communications.”