User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 6-66
■ Communication address setting
SEt17
CoM
Setting content
Initial value
4
AdR
TOHO protocol
1 to 99 (stations)
1
MODBUS protocol
1 to 247 (stations)
Set the address for communication.
Take care that no identical numbers are assigned for more than one unit of equipment.
For details of communication, see “TTM-200 series operation manual - communications.”
■ Response delay time setting
SEt17
CoM
Setting content
Initial value
5
AWt
0 to 250 (ms)
0
Set the response delay time in communication.
Response delay time in communication is set for the time taken from when a host computer completes transmission of
“request message” until when it gives up the line to become in the input state.
Note Communication may not be properly executed when the response delay time setting is for too short a time.
Note For the actual operation time, processing time of the product is added on the response delay time.
For details of communication, see “TTM-200 series operation manual - communications.”
■ Communication switchover setting
SEt17
CoM
Setting content
Initial value
6
Mod
0
Write inhibit
1
1
Writable
2
Concurrent temperature ascent master
3
Concurrent temperature ascent slave
Set the communication switchover.
When “0” is set, writing is inhibited.
When “1” is set, writing is enabled.
When “2” is set, master for the concurrent temperature ascent is established.
When “3” is set, slave for the concurrent temperature ascent is established.
For details of communication, see “TTM-200 series operation manual - communications.”