User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 6-74
■Program Mode Setting / Power Failure Compensation Range Setting
SEt21
PGF
Setting Contents
Initial
Value
2
PGMd
Program Mode Setting 3
0
0
Program 1(w/o Power Failure Compensation)
1
Program 2(w/o Power Failure Compensation)
2
Program 1(w/ Power Failure Compensation)
3
Program 2(w/ Power Failure Compensation)
※Program 1:After the operation, control stops.
※Program 2: After the operation, the control continues.
3
PoC
Power Failure Compensation Range Setting
<Always resume at 0> 3
0
During Temperature Input
0~999(0.0~999.9)(℃)
During Analog Input
0
0~9999 (digit)
*2 Program Mode Setting (PGMd)
This is to set the operation condition of “POWER FAILURE COMPENSATION WITH / WITHOUT” setting
and “PROGRAM OPERATION END” during the program mode.
Setting Range
0: Program 1 (Without Power Failure Compensation)
1: Program 2 (Without Power Failure Compensation)
2: Program 1 (With Power Failure Compensation)
3: Program 2 (With Power Failure Compensation)
Program 1: The control stops after ending the program operation.
END indication appears after the operation. After the END indication appears, the control will stop.
Program 2: The control continues after ending the program operation.
The END indication appears after the operation, but the control will continue.
Operate the key or use DI to stop the control.
NOTE: The SET4 Control Mode Setting (Md) becomes ineffective with Program Mode (C/P=1). This is effective only
with Constant Operation.
Re: Power Failure Compensation
This is a function in which, when the power recovers, the operation restarts from the STEP before the power failure when
the function is set to “With Power Failure Compensation”. The present step, repeat no. of times, remaining time is being
stored.
When the setting condition of the Power Failure Compensation Rage Setting (PoC) has been satisfied, it will return to the
condition last stored by the STEP, and the operation restarts.
*3 Power Failure Compensation Range Setting (PoC)
This is to set the PV value range of the recovery decision during the power recovery.
Setting Range
Temperature Input (℃) 0 – 999 (0.0 – 999.9)
Analog Input (digit) 0 – 9999
NOTE: The condition of recovery is when the difference between the PV value at the time of recovery and the PV value
before the power failure is smaller than the power failure compensation range setting (PoC).
PoC ≧ (PV value at the time of recovery) – (PV value before the power failure)
NOTE: After the power recovery, when the sensor is either disconnected or defective, the recovery action will not take
place regardless of the PoC setting value. The operation condition will be “Program Operation Stop”.