User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 6-77
6.14 PROGRAM SETTING
■Setting No. of Steps to be Used / Step SV* Setting / Step Time* Setting
SEt22
PROG
SETTING CONTENTS
INITIAL
VALUE
1
StEPN
Setting of no. of steps used 3
8
Setting Value Range n=1~8
2
St*bK
Step* Designated Bank Setting 3
0
Setting Value Range St*BK=0~7
*=1~(StEPN Setting Value)
3
SV*
Step SV* Setting 3
0
Setting Value Range SV*=SLL~SLH
*=1~(StEPN Setting Value)
※When the SLL and SLH is set at the Bank, the
value of the SLL,SLH will be set on each bank.
4
tIM*
Step Time* Setting 3
00:00
Setting Value Range TIM*=00:00~99:59
*=1~(StEPN Setting Value)
Sets the Program Step Data of the Program Setting Mode.
*1 No. of Steps Used Setting (StEPN)
This is to set the “Max. No. of Steps” which is used in the programmed operation.
*2 Step* Designated Bank Setting (St*bK)
This is to set the “Bank Nos.” which the system refers in every step.
*3 Step SV* Setting (SV*)
This is to set the target value (temperature or analog value) of the control in every steps.
*4 Step Time* Setting (tIM*)
This is to set the Step Duration Time of every steps.
The next page shows the behavior diagram of the “No. of Steps Used Setting / Step SV* Setting / Step Time* Setting”.