User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 6-79
■Repeat Start Step Setting / Repeat End Step Setting / Setting the Times of Execution / Setting the no. of
Execusion / No. of Times Monitor
SEt22
PROG
Setting Contents
Initial
Value
5
StRSt
Repeat Start Step Setting 3
1
Setting Value Range 1~Repeat End Step Setting
(ENdSt)
6
ENdSt
Repeat End Step Setting 3
StEPN
Repeat Start Step Setting (StRSt StRSt)~
Setting No. of Steps to be used or StEPN
※When set to StEPN, the value which is set under the
Setting No. of Steps to be Used will be “Repeat End Step
Setting”.
7
RUNP
No. of Execution Setting / No. of Execution Monitor 3
1
Setting Value Range RUNP=0~9999
(When RUNP=0, Infinite)
Setting the condition of repeated operation during the programmed operation
*5 Repeated Start Step Setting (StRSt)
This is to set the starting point of the repetition (Step No. of which the repetition starts)
*6 Repeated End Step Setting (ENdSt)
This is to set the end point of the repetition (Step No. of which the repetition ends)
*7 Setting No. of Executions / No. of Executions Monitor (RUNP)
This is to set the no. of time of repetition at the start point and end point.
NOTE: The setting value of the “No. of Executions Setting ” and “No. of Executions” done will be shown alternately only
on the display of the controller unit.
■Repeat Operation Behavior Diagram
STEP1 STEP2 STEP3 STEP2 STEP3 STEP2 STEP3 STEP4
programmed
operation
start
Repeated Start Step Setting : STEP2
Repeated End Step Setting : STEP3
Setting No. of Executions : 3 times
programmed
operation
end
Above is usage example of Repeat Operation Function