User Manual

Table Of Contents
48-7009-E 7-4
(2) Control output section
1) No. of output points
2 points
2) Output type (fixed per model designation)
Relay contact output
a) Contact type 1a contact
b) Contact capacity 250 VAC, 3A (resistance loads)
c) Min. loads 5 VDC, 100 mA
d) Mechanical life 5 million counts or more
e) Electric life 100 thousand counts or more
(More than 80 thousand counts at the UL approval)
f) Isolation Isolated from power circuit and CPU circuit
Voltage output for SSR drive
a) Output type ON/OFF
b) Output voltage 12 VDC
c) Output voltage accuracy ±1 V (23 ± 10 °C)
d) Load resistance 600 or larger
e) Leak current 21 μA or smaller (at output off)
f) Isolation Isolated from power circuit and CPU circuit
Open collector output
a) Output type Open collector
b) Output rating 24 VDC, 100 mA
c) Leak current 0.3 mA or smaller (at output tuned off)
d) Residual voltage 3 V or smaller (at output tuned on)
e) Isolation Isolated from power circuit and CPU circuit
Voltage 0 - 1 VDC output
a) Output type Continuous
b) Output accuracy ±0.3 % (23 ± 10 °C)
c) Output resolution Better than display resolution
d) Load resistance 500 k or larger
e) Isolation Isolated from power circuit and CPU circuit
Voltage 0 - 5 VDC output
a) Output type Continuous
b) Output accuracy ±0.3 % (23 ± 10 °C)
c) Output resolution Better than display resolution
d) Load resistance 1 k or larger
e) Isolation Isolated from power circuit and CPU circuit
Voltage 1 - 5 VDC output
a) Output type Continuous
b) Output accuracy ±0.3 % (23 ± 10 °C)
c) Output resolution Better than display resolution
d) Load resistance 1 k or larger
e) Isolation Isolated from power circuit and CPU circuit
Voltage 0 - 10 VDC output
a) Output type Continuous
b) Output accuracy ±0.3 % (23 ± 10 °C)
c) Output resolution Better than display resolution
d) Load resistance 1 k or larger
e) Isolation Isolated from power circuit and CPU circuit
Voltage 0 - 10 mVDC output
a) Output type Continuous
b) Output accuracy ±0.3 % (23 ± 10 °C)
c) Output resolution Better than display resolution
d) Load resistance 500 k or larger
e) Isolation Isolated from power circuit and CPU circuit
Voltage 4 - 20 mADC output
a) Output type Continuous
b) Output accuracy ±0.3 % (23 ± 10 °C)
c) Output resolution Better than display resolution
d) Load resistance 600 k or smaller
e) Isolation Isolated from power circuit and CPU circuit
3) Connection method
Terminal block