User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 7-12
Symptom
Description
Check item
Control unstable
* Overshoot
* Undershoot
* Hunting
(1) ON/OFF control is selected.
At factory shipment, the setting is PID control.
ON/OFF control is set in the bank 1.
(2) Proportional cycle is long, compared to
ascent/descent speed of temperature.
(3) PID constant is inappropriate.
(1) Change the control type from ON/OFF control
to PID control (self-tuning/auto-tuning) in the
setting mode of SET 4, item 6.
For self-tuning, turn on the power supplies for
this product and load side simultaneously or
for load side first.
(2) Set the proportional cycle shorter.
Controllability is better as the proportional
cycle is shorter, however, take into account life
of relays in case of the use of relay output.
(3) Change the PID constant.
1) Re-execute auto-tuning.
2) Manually set the PID constant.
No operation
(1) Control mode is set to READY.
(2) The setting is “control stop” due to assignment
of the function key for “control start/stop.”
(1) Set the control mode to RUN in the setting
mode of SET 4, item 5. Currently, display
lamp is lighting as RDY, indicating the state of
control stop.
(2) Have the state of control start by a single
press of the FUNC key.
Key ineffective
(1) Key lock is set.
(1) Check the setting of key lock in the key
function setting mode of SET 3, item 6.
No event output is
provided.
(1) Setting of each item for event output is
inappropriate.
(2) Event setting value is inappropriate.
(1) Check settings related to the event output.
1) Target connection setting
2) Event function 1 setting
3) Event function 2 setting
4) Event function 3 setting
5) Event function 4 setting
6) Event delay timer
7) Event polarity setting
(2) Check the event upper limit/lower limit value.
No loader
communication
possible
(1) Loader cable is not correctly connected.
(2) Dedicated loader software is not appropriately
installed.
(3) Communication port does not fit the personal
computer (PC).
(1) Check the loader cable connection.
(2) Re-install the dedicated loader software.
(3) Re-check the communication port on the PC
and re-set the communication port on the
software side.
Function key
ineffective
(1) Key lock is set.
(2) A pressing time is set for the function key.
(1) Check the setting of key lock in the key
function setting mode of SET 3, item 6.
(2) Check the pressing time of the function key in
the function key function setting mode of SET
3, item 1.
No timer operation
(1) Timer stop is set in the DI function.
(2) Target connection setting is inappropriate.
(1) Check the setting of DI, ON or OFF.
(2) Check that the target connection of the target
connection setting corresponds to timer.
No stop of event
(1) Hold function is set for the event function
setting.
(1) Check that the Hold function is set for each
event function setting.